Knowledge

Substation

Source 📝

899:. Although it is the most expensive, these gases are a much more effective insulator than air. GIS require only 10 to 20 percent of the land area as AIS, which can save on land acquisition cost in urban areas, and allow the substation to be built at the exact location where its power is being used in an industrial or urban area—which can be a significant cost savings. On the generation side, GIS can be installed closer to the generator which allows cost savings in cabling, bus duct connections, and civil construction and can increase reliability. GIS can replace AIS if power requirements increase without requiring additional land area. Additionally, GIS is commonly installed in an enclosed building that keeps the equipment protected from pollution and salt. Unless the substation is often used for switching, maintenance cost can be very low or even zero for many years. Because SF 622: 505: 493: 170: 477: 296: 27: 470:, which is the connecting and disconnecting of transmission lines or other components to and from the system. Switching events may be planned or unplanned. A transmission line or other component may need to be de-energized for maintenance or for new construction, for example, adding or removing a transmission line or a transformer. To maintain reliability of supply, companies aim at keeping the system up and running while performing maintenance. All work to be performed, from routine testing to adding entirely new substations, should be done while keeping the whole system running. 199: 681: 190:. Most commonly, the utility does the engineering and procurement while hiring a contractor for actual construction. Major design constraints for construction of substations include land availability and cost, limitations on the construction period, transportation restrictions, and the need to get the substation running quickly. Prefabrication is a common way to reduce the construction cost. For connecting the new substation, a partial outage at another substation may be required, but the utility often tries to minimize downtime. 699:. In some cases, the lines will not have both, with either a switch or a circuit breaker being all that is considered necessary. A disconnect switch is used to provide isolation, since it cannot interrupt load current. A circuit breaker is used as a protection device to interrupt fault currents automatically, and may be used to switch loads on and off, or to cut off a line when power is flowing in the 'wrong' direction. When a large fault current flows through the circuit breaker, this is detected through the use of 634: 344: 87: 606: 2235: 107: 2814: 703:. The magnitude of the current transformer outputs may be used to trip the circuit breaker resulting in a disconnection of the load supplied by the circuit break from the feeding point. This seeks to isolate the fault point from the rest of the system, and allow the rest of the system to continue operating with minimal impact. Both switches and circuit breakers may be operated locally (within the substation) or remotely from a supervisory control center. 753: 215: 692:, which shows in simplified form the switching and protection arrangement required, as well as the incoming supply lines and outgoing feeders or transmission lines. It is a usual practice by many electrical utilities to prepare one-line diagrams with principal elements (lines, switches, circuit breakers, transformers) arranged on the page similarly to the way the apparatus would be laid out in the actual station. 336: 770:. To this is added the necessary space for employees to work safely and vehicles to pass. Sometimes it is necessary to work on parts of the substation while energized, but employees must maintain a safe distance of at least 3 metres (9.8 ft). The aim to reduce substation footprints comes into conflict with ease of maintenance enhanced by including gaps where employees can safely work. 979:
when there is any unusual activity, to help reconstruct what happened after the fact. These control rooms typically are heated and air conditioned to ensure the reliable operation of this equipment. Additional equipment is necessary to handle power surges associated with intermittent renewable energy such as dispersed generation from wind or solar.
913:(called OCB for oil circuit breaker) provides a high resistance between the opened contacts, effectively stopping the flow of current. Although oil circuit breakers are suitable for a wide range of voltages, the oil becomes contaminated during the suppression of arcs and must be filtered or replaced periodically. 1001:
finds hot spots in the substation where electrical energy is being converted to heat, which indicates a problem and can cause additional damage from the high heat. Dissolved gas analysis can tell when an oil-insulated transformer needs to have the oil filtered or replace, and also detect other issues.
1015:
Early electrical substations required manual switching or adjustment of equipment, and manual collection of data for load, energy consumption, and abnormal events. As the complexity of distribution networks grew, it became economically necessary to automate supervision and control of substations from
1000:
Maintenance of substations involves inspections, data collection and analysis, and routine scheduled work. Using methods such as infrared scanning and dissolved gas analysis, it can be predicted when the substation will need maintenance and predict dangers before they materialize. Infrared technology
978:
Larger substations have control rooms for the equipment used to monitor, control, and protect the rest of the substation equipment. It often contains protective relays, meters, breaker controls, communications, batteries, and recorders that save detailed data about substation operations, particularly
834:
Substations may be on the surface in fenced enclosures, underground, or special-purpose buildings. High-rise buildings may have several indoor substations. Indoor substations are usually found in urban areas to reduce the noise from transformers, improve appearance, or protect switchgear from extreme
987:
Most transformers lose between 5 and 1.5 percent of their input as heat and noise. Iron losses are no-load and constant whenever the transformer is energized, while copper and auxiliary losses are proportionate to the square of the current. Auxiliary losses are due to running fans and pumps which is
879:
Air at atmospheric pressure (air-insulated switchgear (AIS)), which is the most common worldwide. Air is the cheapest insulator and is easy to modify, but AIS takes up more space, and leaves equipment exposed to the outside environment. One drawback of AIS is the visual impact of a larger substation
781:
in some countries, is used to ground circuits that are being worked on to prevent accidental re-energization while workers are in contact with a de-energized circuit. Often, earth rods are driven deeper into the ground from the grounding grid for lower resistance grounding, and may be surrounded by
766:
Based on the jurisdiction or company, there are safety standards with minimum required clearance between different live equipment or conductors or between live metal and the ground, which often varies with higher clearance being required for higher voltages because of the greater ability to generate
451:
A switching station is a substation without transformers and operating only at a single voltage level. Switching stations are sometimes used as collector and distribution stations. Sometimes they are used for switching the current to back-up lines or for parallelizing circuits in case of failure. An
363:
The input for a distribution substation is typically at least two transmission or sub-transmission lines. Input voltage may be, for example, 115 kV, or whatever is common in the area. The output is a number of feeders. Distribution voltages are typically medium voltage, between 2.4 kV and
845:
Outdoor, above-ground substation structures include wood pole, lattice metal tower, and tubular metal structures, although other variants are available. Where space is plentiful and appearance of the station is not a factor, steel lattice towers provide low-cost supports for transmission lines and
765:
Because of the risk of electrical shock, substations are inherently dangerous to electrical workers. To mitigate this hazard, substations are designed with various safety features. Live conductors and bare equipment are kept separate, either with protected equipment, or using screens or distance.
748:
The arrangement of switches, circuit breakers, and buses used affects the cost and reliability of the substation. For important substations a ring bus, double bus, or so-called "breaker and a half" setup can be used, so that the failure of any one circuit breaker does not interrupt power to other
652:
Selection of the location of a substation must consider many factors. Sufficient land area is required for installation of equipment with necessary clearances for electrical safety, and for access to maintain large apparatus such as transformers. The site must have room for expansion due to load
870:
are commonly used to interrupt the flow of current in substation equipment. At the time of interruption, current could be normal, too high due to excessive load, unusual due to a fault, or tripped by protective relays prior to anticipated trouble. The most common technologies to extinguish the
790:
to further reduce resistance and ensure effective grounding for the lifetime of the substation. Above ground, the grounding conductors may be steel, aluminum, or copper. They must be thick enough to carry the expected current of a fault for 1-3 seconds and remain undamaged. Substation fences,
359:
transfers power from the transmission system to the distribution system of an area. It is uneconomical to directly connect electricity consumers to the main transmission network, unless they use large amounts of power, so the distribution station reduces voltage to a level suitable for local
930:
are similar to breakers, and can be cheaper because they do not require separate protective relays. Often used in distribution, they often are programmed to trip when the amps exceed a certain amount over a period of time. Reclosers will attempt to re-energize the circuit after a delay. If
403:
up into the transmission grid. Usually for economy of construction the collector system operates around 35 kV, although some collector systems are 12 kV, and the collector substation steps up voltage to a transmission voltage for the grid. The collector substation can also provide
374:
The downtown areas of large cities feature complicated distribution substations, with high-voltage switching, and switching and backup systems on the low-voltage side. More typical distribution substations have a switch, one transformer, and minimal facilities on the low-voltage side.
271:
connects two or more transmission lines. The simplest case is where all transmission lines have the same voltage. In such cases, substation contains high-voltage switches that allow lines to be connected or isolated for fault clearance or maintenance. A transmission station may have
660:
The substation site must be reasonably central to the distribution area to be served. The site must be secure from intrusion by passers-by, both to protect people from injury by electric shock or arcs, and to protect the electrical system from misoperation due to vandalism.
538:
The function of the switching station is to isolate the faulty portion of the system in the shortest possible time. De-energizing faulty equipment protects it from further damage, and isolating a fault helps keep the rest of the electrical grid operating with stability.
991:
Oil-based transformers are often built with bunded areas to prevent the escape of flaming or leaking oil. Fire separation areas or firewalls are built around the transformer to stop the spread of fire. Firefighting vehicles are allowed a path to access the area.
791:
typically at least 2 metres (6 ft 7 in) in height, both protect the public from electrical hazards and also protect the substation from vandalism. Internal fences can also be incorporated to protect employees from areas that are unsafe when energized.
143:
to change voltage levels between high transmission voltages and lower distribution voltages, or at the interconnection of two different transmission voltages. They are a common component of the infrastructure. There are 55,000 substations in the United States.
162:. As central generation stations became larger, smaller generating plants were converted to distribution stations, receiving their energy supply from a larger plant instead of using their own generators. The first substations were connected to only one 492: 850:(at high voltages, with gas insulated switchgear), or use metal-enclosed or metal-clad switchgear at lower voltages. Urban and suburban indoor substations may be finished on the outside so as to blend in with other buildings in the area. 364:
33 kV, depending on the size of the area served and the practices of the local utility. The feeders run along streets overhead (or underground, in some cases) and power the distribution transformers at or near the customer premises.
138:
from high to low, or the reverse, or perform any of several other important functions. Between the generating station and consumer, electric power may flow through several substations at different voltage levels. A substation may include
1016:
a centrally attended point, to allow overall coordination in case of emergencies and to reduce operating costs. Early efforts to remote control substations used dedicated communication wires, often run alongside power circuits.
463:. In this case the generators from the power station supply their power into the yard onto the generator bus on one side of the yard, and the transmission lines take their power from a Feeder Bus on the other side of the yard. 351:, Canada, disguised as a house, complete with a driveway, front walk and a mown lawn and shrubs in the front yard. A warning notice can be clearly seen on the "front door". Disguises for substations are common in many cities. 569:(AC) at frequencies other than that of the public grid. Sometimes they are also transmission substations or collector substations if the railway network also operates its own grid and generators to supply the other stations. 749:
circuits, and so that parts of the substation may be de-energized for maintenance and repairs. Substations feeding only a single industrial load may have minimal switching provisions, especially for small installations.
1048:, to list a few, are used to allow multiple intelligent electronic devices to communicate with each other and supervisory control centers. Distributed automatic control at substations is one element of the so-called 857:
is generally an outdoor substation built in a metal enclosure, in which each item of the electrical equipment is located very near to each other to create a relatively smaller footprint size of the substation.
439:, or interconnected non-synchronous networks. These stations contain power electronic devices to change the frequency of current, or else convert from alternating to direct current or the reverse. Formerly 922:
Mixed, including both gas and air insulation. Although it’s the least common option it can be useful when an air-insulated substation needs to be expanded but there is very limited location for additional
1407: 756:
This single-line diagram illustrates the breaker-and-a-half configuration often used in switchyards of small utilities. In large utilities the double-bus-double-breaker configuration is often preferred.
1069: 966:
or enabling extra power to be sent through the conductors. Capacitors may be left on in response to constant inductive load or turned on when inductive load is increased, such as in the summer for
311:. The largest transmission substations can cover a large area (several acres/hectares) with multiple voltage levels, many circuit breakers, and a large amount of protection and control equipment ( 919:
is a better insulator than air but less than gas or oil. Vacuum circuit breakers (VCB) are smaller than air circuit breakers and are commonly used in distribution and other switchgear under 35kv.
367:
In addition to transforming voltage, distribution substations also isolate faults in either the transmission or distribution systems. Distribution substations are typically the points of
988:
noisy when the transformer is operating at maximum capacity. To reduce noise, enclosures are often built around the transformer and can also be added after the substation is built.
476: 880:
with overhead power lines entering and exiting, which may be unacceptable in scenic or urban areas. AIS requires additional bracing in a seismically active area, and emits more
147:
Substations may be owned and operated by an electrical utility, or may be owned by a large industrial or commercial customer. Generally substations are unattended, relying on
504: 411:
Collector substations also exist where multiple thermal or hydroelectric power plants of comparable output power are in proximity. Examples for such substations are
1036:
made for an exponential increase in the number of points that could be economically controlled and monitored. Today, standardized communication protocols such as
726:
are used to protect substation equipment accordingly. Insulation Coordination studies are carried out extensively to ensure equipment failure (and associated
625:
Substation in a castle-like building from the 1910s serves as distribution point next to the Lésna dam. It is one of several hydroelectric stations at the
641:
Substation design is aimed at minimizing cost while ensuring power availability and reliability, and enabling changes to the substation in the future.
773:
Underneath a substation, a mat or grid of conductors laid around 0.5 or 0.6 metres (1 ft 8 in or 2 ft 0 in) underground provides
553:
Electrified railways also use substations, often distribution substations. In some cases a conversion of the current type takes place, commonly with
498:
Former high-voltage substation in Stuttgart, Germany, now 110 kV switching station. The 220 kV level is eliminated for grid simplification.
1280: 597:. Mobile substations are usually rated much lower than permanent installations, and may be built in several units to meet road travel limitations. 903:
turns to solid around −40 °C (−40 °F), in some climates these circuit breakers require heaters to function in extremely cold weather. SF
408:
if it is needed, metering, and control of the wind farm. In some special cases a collector substation can also contain an HVDC converter station.
947: 2086: 423:-fired power plants. If no transformers are required for increasing the voltage to transmission level, the substation is a switching station. 395:, a collector substation may be required. It resembles a distribution substation although power flow is in the opposite direction, from many 2759: 371:, although on long distribution circuits (of several miles/kilometers), voltage regulation equipment may also be installed along the line. 842:
as conductors between electrical equipment. Busbars may be aluminum tubing 3–6 inches (76–152 mm) thick, or else wires (strain bus).
110:
A 115 kV to 41.6/12.47 kV 5 MVA 60 Hz substation with circuit switcher, regulators, reclosers and control building at
872: 846:
apparatus. Low-profile substations may be specified in suburban areas where appearance is more critical. Indoor substations may be
617:
is Canada's oldest substation. It has a facade in clay brick with gray stone ornaments to blend in to its downtown environment.
99: 2055: 2036: 1961: 1939: 1845: 1811: 1792: 1773: 1754: 1728: 1700: 1613: 1594: 1563: 1393: 1374: 1184: 1165: 1146: 1127: 281: 2817: 2234: 102:, each with a capacity of 150 MVA. This substation uses steel lattice structures to support strain bus wires and apparatus. 1096: 2656: 2764: 2079: 459:
A switching station may also be known as a switchyard, and these are commonly located directly adjacent to or nearby a
1328: 2384: 1438: 621: 2838: 2547: 2472: 2343: 799:
Substations generally have switching, protection and control equipment, and transformers. In a large substation,
303:
Transmission substations can range from simple to complex. A small "switching station" may be little more than a
1070:"Joint Consultation Paper: Western Metropolitan Melbourne Transmission Connection and Subtransmission Capacity" 308: 653:
growth or planned transmission additions. Environmental effects of the substation must be considered, such as
2719: 2651: 2641: 2517: 2417: 2072: 589:. They are designed to be compact for travel on public roads, and are used for temporary backup in times of 2572: 2532: 2109: 815:
for protection of distribution circuits. Substations themselves do not usually have generators, although a
169: 2799: 2794: 2512: 2487: 2477: 2453: 2448: 2154: 432: 244: 231: 159: 131: 127: 20: 2714: 2432: 2402: 2179: 962:) are added to the system. Capacitors can reduce the current in wires, helping stem system losses from 707: 392: 581:
is a substation on wheels, containing a transformer, breakers and buswork mounted on a self-contained
2769: 2258: 2219: 516: 227: 2744: 2552: 2492: 2149: 1017: 955: 931:
unsuccessful for a few times, the recloser will have to be manually reset by an electrical worker.
847: 644:
Substations may be built outdoors, indoors, or underground or in a combination of these locations.
316: 610: 2683: 2673: 2663: 1010: 719: 405: 339:
Transformer tower in Germany. Medium voltage supply at the front, low voltage output on the side.
2604: 2467: 2250: 2139: 1021: 881: 384: 312: 285: 123: 1408:
Electricity Substation Leases: Considerations for Utility Companies, Landowners and Developers
1301: 295: 114:. It shows elements of low-profile construction, with apparatus mounted on individual columns. 2739: 2507: 2502: 2482: 664:
If not owned and operated by a utility company, substations are typically occupied on a long
2333: 2095: 1250: 951: 774: 277: 807:
or overload currents that may occur on the network. Smaller distribution stations may use
26: 8: 2704: 2537: 2437: 2412: 2365: 2174: 2164: 2129: 1412: 888: 700: 566: 548: 251: 198: 733:
Once past the switching components, the lines of a given voltage connect to one or more
2578: 2189: 828: 669: 531: 368: 289: 187: 323:
systems). Modern substations may be implemented using international standards such as
2729: 2609: 2214: 2051: 2032: 1434: 824: 812: 416: 111: 680: 2678: 2619: 2323: 2318: 2295: 2204: 2144: 1028:
cables as well as dedicated wired remote control circuits have all been applied to
689: 590: 562: 483: 443:
changed frequency to interconnect two systems; nowadays such substations are rare.
440: 436: 2709: 2668: 2646: 2527: 2497: 2462: 2422: 2224: 967: 887:
Gas (gas circuit breaker (GCB) or gas-insulated switchgear (GIS)), most commonly
867: 800: 778: 696: 237: 166:, where the generators were housed, and were subsidiaries of that power station. 2734: 2724: 2522: 2134: 1097:"Attacks on Pacific north-west power stations raise fears for US electric grid" 1033: 943: 723: 558: 467: 453: 255: 633: 2832: 2754: 2542: 2427: 2407: 2338: 2328: 2285: 2169: 2124: 1025: 804: 715: 460: 343: 163: 86: 98:, showing three of the five 220 kV/66 kV transformers, as well as 2774: 2749: 2614: 2583: 2397: 2199: 963: 959: 808: 727: 614: 605: 586: 582: 524: 396: 2599: 2567: 2360: 2348: 2268: 2194: 2184: 2114: 1281:"Lights On but Nobody Home: Behind the Fake Buildings that Power Chicago" 970:. The switching may be remote and can be done manually or automatically. 946:(such as motors, transformers, and some industrial equipment) with their 910: 816: 742: 273: 140: 106: 2562: 2557: 2370: 2353: 2209: 2064: 2046:
Finn, John (2019). "Introduction to Substation Planning and Concepts".
1049: 942:
banks are used in substations to balance the lagging current draw from
688:
The first step in planning a substation layout is the preparation of a
412: 183: 2278: 2273: 2159: 2119: 1244: 1242: 1240: 1041: 939: 820: 787: 783: 767: 752: 745:
electrical power distribution is largely universal around the world.
711: 554: 400: 388: 324: 95: 91: 222:
Substations typically serve at least one of the following purposes:
214: 2392: 927: 654: 186:
or alternately all phases of its development may be handled by the
1237: 695:
In a common design, incoming lines have a disconnect switch and a
2313: 2303: 420: 348: 135: 626: 2308: 2029:
Electric Power System Basics for the Nonelectrical Professional
1601: 1582: 1076:. Powercor Australia, Jemena, Australian Energy Market Operator 1045: 916: 839: 738: 734: 304: 203: 1951: 1949: 1553: 1551: 1549: 1381: 1362: 668:
such as a renewable 99-year lease, giving the utility company
335: 1029: 665: 320: 148: 519:
in a transmission line or any other component, for example:
419:
in the Czech Republic, where power is collected from nearby
158:
comes from the days before the distribution system became a
2263: 1946: 1927: 1833: 1546: 1431:
Standard Handbook for Electrical Engineers Eleventh Edition
1037: 684:
Tottenham Substation, set in wild parkland in North London.
510:
High-voltage switching station in Washington, United States
207: 16:
Part of an electrical transmission, and distribution system
1744: 1742: 1740: 1738: 777:. This grid, which is typically copper although it may be 292:
to control power flow between two adjacent power systems.
594: 2031:. IEEE Press Series on Power and Energy Systems. Wiley. 243:
Reducing the voltage from transmission to lower-voltage
1799: 1780: 1761: 1735: 1718: 1716: 1714: 1712: 1710: 1690: 1688: 1686: 875:
from separating the conductors in the breaker include:
1903: 1881: 1879: 1823: 1821: 1673: 1671: 1474: 1534: 1498: 1486: 1464: 1462: 1227: 1225: 173:
220 kV/110 kV/20 kV station in Germany
2050:. Springer International Publishing. pp. 7–10. 1707: 1683: 819:
may have a substation nearby. Other devices such as
2004: 1992: 1876: 1864: 1852: 1818: 1668: 1656: 1644: 1212: 1210: 1208: 1206: 1172: 1153: 1134: 1115: 486:, United States, 2006. This is a 500 kV switchyard. 466:An important function performed by a substation is 1980: 1968: 1915: 1891: 1632: 1620: 1570: 1522: 1510: 1459: 1447: 1392:sfn error: no target: CITEREFGlaubitz_et_al.2018 ( 1373:sfn error: no target: CITEREFGlaubitz_et_al.2018 ( 1350: 1320: 1222: 1191: 722:failures into substation equipment. Line entrance 950:. Additional capacitor capacity may be needed if 2830: 1203: 1032:(SCADA) for substations. The development of the 247:lines that supply individual homes or businesses 1960:sfn error: no target: CITEREFNixon_et_al.2018 ( 1938:sfn error: no target: CITEREFNixon_et_al.2018 ( 1844:sfn error: no target: CITEREFNixon_et_al.2018 ( 1612:sfn error: no target: CITEREFNixon_et_al.2018 ( 1593:sfn error: no target: CITEREFNixon_et_al.2018 ( 1562:sfn error: no target: CITEREFNixon_et_al.2018 ( 1387: 1368: 234:over long distances, using step-up transformers 55:Transformer for measurement of electric voltage 276:to convert between two transmission voltages, 2080: 431:Converter substations may be associated with 1955: 1933: 1839: 1607: 1588: 1557: 907:has been used in switchgear since the 1960s. 1810:sfn error: no target: CITEREFGlaubitz2018 ( 1791:sfn error: no target: CITEREFGlaubitz2018 ( 1772:sfn error: no target: CITEREFGlaubitz2018 ( 1753:sfn error: no target: CITEREFGlaubitz2018 ( 523:a line is hit by lightning and develops an 515:Unplanned switching events are caused by a 182:Substations may be designed and built by a 2087: 2073: 1420:, 26 January 2018, accessed 22 August 2023 954:(such as small diesel generators, rooftop 452:example is the switching stations for the 330: 262: 1727:sfn error: no target: CITEREFTwomey2018 ( 1699:sfn error: no target: CITEREFTwomey2018 ( 1278: 1260:. United States Department of Agriculture 2094: 1805: 1786: 1767: 1748: 1183:sfn error: no target: CITEREFOkada2018 ( 1164:sfn error: no target: CITEREFOkada2018 ( 1145:sfn error: no target: CITEREFOkada2018 ( 1126:sfn error: no target: CITEREFOkada2018 ( 1094: 1030:Supervisory Control and Data Acquisition 884:and noise than alternative technologies. 751: 679: 637:15 kV/400 V distribution tower in Poland 632: 620: 609:In continuous operation since 1901, the 604: 426: 342: 334: 294: 284:devices such as capacitors, reactors or 213: 197: 168: 105: 85: 25: 1326: 741:, usually in multiples of three, since 378: 2831: 1722: 1694: 100:high-voltage transformer fire barriers 90:A 50 Hz electrical substation in 2068: 2026: 2010: 1998: 1909: 1885: 1870: 1858: 1827: 1677: 1662: 1650: 1423: 1231: 1178: 1159: 1140: 1121: 831:may also be located at a substation. 647: 2045: 1986: 1974: 1921: 1897: 1638: 1626: 1576: 1540: 1528: 1516: 1504: 1492: 1480: 1468: 1453: 1356: 1279:Steinberg, Neil (13 December 2013). 1251:"Design Guide for Rural Substations" 1248: 1216: 1197: 895:) or a mixture of gases including SF 572: 446: 151:for remote supervision and control. 1095:Anguiano, Dani (10 December 2022). 226:Increasing the voltage produced by 13: 2765:Renewable energy commercialization 2020: 675: 657:, noise and road traffic effects. 14: 2850: 2813: 2812: 2233: 1429:Donald G. Fink, H. Wayne Beatty 973: 503: 491: 475: 313:voltage and current transformers 1400: 1338:. IEEE Power and Energy Society 1294: 1272: 982: 848:gas insulated substations (GIS) 177: 1088: 1062: 995: 134:system. Substations transform 1: 2760:Renewable Energy Certificates 2720:Cost of electricity by source 2642:Arc-fault circuit interrupter 2518:High-voltage shore connection 1055: 1004: 934: 861: 794: 347:A distribution substation in 299:Minimal HV station in Germany 2775:Spark/Dark/Quark/Bark spread 2573:Transmission system operator 2533:Mains electricity by country 2110:Automatic generation control 7: 2800:List of electricity sectors 2795:Electric energy consumption 2513:High-voltage direct current 2488:Electric power transmission 2478:Electric power distribution 2155:Energy return on investment 1406:Chapman, A. and Broom, R., 708:overhead transmission lines 542: 534:is blown down by high wind. 290:phase shifting transformers 202:High-voltage substation in 122:is a part of an electrical 39:Secondary power lines' side 21:Substation (disambiguation) 10: 2855: 2715:Carbon offsets and credits 2433:Three-phase electric power 1416:, originally published by 1327:Boyd, Dan; Rampaul, Glen. 1008: 803:are used to interrupt any 585:, meant to be pulled by a 546: 393:photovoltaic power station 18: 2808: 2783: 2770:Renewable Energy Payments 2693: 2630: 2592: 2446: 2383: 2294: 2259:Fossil fuel power station 2249: 2242: 2231: 2102: 1336:IEEE Winnipeg PES Chapter 956:photovoltaic solar panels 809:recloser circuit breakers 760: 600: 228:electric power generation 36:Primary power lines' side 2553:Single-wire earth return 2493:Electrical busbar system 2150:Energy demand management 1302:"Transformer Fire Video" 240:of different power grids 193: 31:Elements of a substation 2684:Residual-current device 2674:Power system protection 2664:Generator interlock kit 1011:Power-system automation 406:power factor correction 357:distribution substation 331:Distribution substation 286:static VAR compensators 282:power factor correction 269:transmission substation 263:Transmission substation 2839:Electrical substations 2468:Distributed generation 2140:Electric power quality 1258:USDA Rural Development 882:electromagnetic fields 838:Substations often use 835:climate or pollution. 757: 685: 638: 630: 618: 385:distributed generation 352: 340: 300: 288:and equipment such as 219: 211: 174: 115: 103: 83: 2740:Fossil fuel phase-out 2508:Electricity retailing 2503:Electrical substation 2483:Electric power system 755: 710:, the propagation of 683: 636: 624: 608: 427:Converter substations 346: 338: 298: 217: 201: 172: 109: 89: 79:Secondary power lines 29: 2096:Electricity delivery 2027:Blume, S.W. (2016). 1388:Glaubitz et al. 2018 1369:Glaubitz et al. 2018 1329:"Mobile Substations" 952:dispersed generation 737:. These are sets of 701:current transformers 379:Collector substation 218:Substation in Russia 19:For other uses, see 2705:Availability factor 2657:Sulfur hexafluoride 2538:Overhead power line 2438:Virtual power plant 2413:Induction generator 2366:Sustainable biofuel 2175:Home energy storage 2165:Grid energy storage 2130:Droop speed control 1610:, pp. 314–315. 1591:, pp. 313–314. 1433:, McGraw Hill 1978 1413:Squire Patton Boggs 889:sulfur hexafluoride 567:alternating current 549:Traction substation 456:transmission line. 387:projects such as a 252:alternating current 64:Current transformer 46:Primary power lines 2579:Transmission tower 2190:Nameplate capacity 1483:, pp. 46, 53. 1249:Stockton, Blaine. 1018:Power-line carrier 855:compact substation 825:voltage regulators 758: 686: 670:security of tenure 648:Location selection 639: 631: 619: 435:converter plants, 369:voltage regulation 353: 341: 325:IEC Standard 61850 301: 220: 212: 188:electrical utility 175: 116: 104: 84: 67:Lightning arrester 2826: 2825: 2730:Environmental tax 2610:Cascading failure 2379: 2378: 2215:Utility frequency 2057:978-3-319-49574-3 2038:978-1-119-18019-7 1956:Nixon et al. 2018 1934:Nixon et al. 2018 1912:, pp. 87–88. 1840:Nixon et al. 2018 1608:Nixon et al. 2018 1589:Nixon et al. 2018 1558:Nixon et al. 2018 1543:, pp. 55–56. 1507:, pp. 48–49. 1495:, pp. 46–47. 1443:Substation Design 579:mobile substation 573:Mobile substation 565:for trains using 563:rotary converters 447:Switching station 441:rotary converters 112:Warren, Minnesota 58:Disconnect switch 2846: 2816: 2815: 2725:Energy subsidies 2679:Protective relay 2620:Rolling blackout 2247: 2246: 2237: 2205:Power-flow study 2145:Electrical fault 2089: 2082: 2075: 2066: 2065: 2061: 2042: 2014: 2008: 2002: 1996: 1990: 1984: 1978: 1972: 1966: 1965: 1953: 1944: 1943: 1931: 1925: 1919: 1913: 1907: 1901: 1895: 1889: 1883: 1874: 1868: 1862: 1856: 1850: 1849: 1837: 1831: 1825: 1816: 1815: 1803: 1797: 1796: 1784: 1778: 1777: 1765: 1759: 1758: 1746: 1733: 1732: 1720: 1705: 1704: 1692: 1681: 1675: 1666: 1660: 1654: 1648: 1642: 1636: 1630: 1624: 1618: 1617: 1605: 1599: 1598: 1586: 1580: 1574: 1568: 1567: 1555: 1544: 1538: 1532: 1526: 1520: 1514: 1508: 1502: 1496: 1490: 1484: 1478: 1472: 1466: 1457: 1451: 1445: 1427: 1421: 1404: 1398: 1397: 1385: 1379: 1378: 1366: 1360: 1354: 1348: 1347: 1345: 1343: 1333: 1324: 1318: 1317: 1315: 1313: 1308:. User Eagle Eye 1298: 1292: 1291: 1289: 1287: 1276: 1270: 1269: 1267: 1265: 1255: 1246: 1235: 1229: 1220: 1214: 1201: 1195: 1189: 1188: 1176: 1170: 1169: 1157: 1151: 1150: 1138: 1132: 1131: 1119: 1113: 1112: 1110: 1108: 1092: 1086: 1085: 1083: 1081: 1066: 968:air conditioners 868:circuit breakers 801:circuit breakers 690:one-line diagram 591:natural disaster 561:(DC) trains, or 507: 495: 484:Grand Coulee Dam 479: 437:traction current 309:circuit breakers 250:Converting from 73:Control building 70:Main transformer 2854: 2853: 2849: 2848: 2847: 2845: 2844: 2843: 2829: 2828: 2827: 2822: 2804: 2788: 2786: 2779: 2710:Capacity factor 2698: 2696: 2689: 2669:Numerical relay 2647:Circuit breaker 2635: 2633: 2626: 2588: 2528:Load management 2498:Electrical grid 2463:Demand response 2456: 2451: 2442: 2423:Microgeneration 2375: 2290: 2238: 2229: 2225:Vehicle-to-grid 2098: 2093: 2058: 2039: 2023: 2021:Further reading 2018: 2017: 2009: 2005: 1997: 1993: 1985: 1981: 1973: 1969: 1959: 1954: 1947: 1937: 1932: 1928: 1920: 1916: 1908: 1904: 1896: 1892: 1884: 1877: 1869: 1865: 1857: 1853: 1843: 1838: 1834: 1826: 1819: 1809: 1804: 1800: 1790: 1785: 1781: 1771: 1766: 1762: 1752: 1747: 1736: 1726: 1721: 1708: 1698: 1693: 1684: 1676: 1669: 1661: 1657: 1649: 1645: 1637: 1633: 1625: 1621: 1611: 1606: 1602: 1592: 1587: 1583: 1575: 1571: 1561: 1556: 1547: 1539: 1535: 1527: 1523: 1515: 1511: 1503: 1499: 1491: 1487: 1479: 1475: 1467: 1460: 1452: 1448: 1428: 1424: 1405: 1401: 1391: 1386: 1382: 1372: 1367: 1363: 1355: 1351: 1341: 1339: 1331: 1325: 1321: 1311: 1309: 1300: 1299: 1295: 1285: 1283: 1277: 1273: 1263: 1261: 1253: 1247: 1238: 1230: 1223: 1215: 1204: 1200:, pp. 7 8. 1196: 1192: 1182: 1177: 1173: 1163: 1158: 1154: 1144: 1139: 1135: 1125: 1120: 1116: 1106: 1104: 1093: 1089: 1079: 1077: 1068: 1067: 1063: 1058: 1022:microwave radio 1013: 1007: 998: 985: 976: 944:inductive loads 937: 906: 902: 898: 894: 864: 797: 779:galvanized iron 763: 724:surge arrestors 697:circuit breaker 678: 676:Design diagrams 650: 611:Adélard-Godbout 603: 575: 551: 545: 511: 508: 499: 496: 487: 480: 454:HVDC Inga–Shaba 449: 429: 415:in Germany and 381: 333: 278:voltage control 265: 238:Interconnection 196: 180: 82: 61:Circuit breaker 42: 24: 17: 12: 11: 5: 2852: 2842: 2841: 2824: 2823: 2821: 2820: 2809: 2806: 2805: 2803: 2802: 2797: 2791: 2789: 2785:Statistics and 2784: 2781: 2780: 2778: 2777: 2772: 2767: 2762: 2757: 2752: 2747: 2742: 2737: 2735:Feed-in tariff 2732: 2727: 2722: 2717: 2712: 2707: 2701: 2699: 2694: 2691: 2690: 2688: 2687: 2681: 2676: 2671: 2666: 2661: 2660: 2659: 2654: 2644: 2638: 2636: 2631: 2628: 2627: 2625: 2624: 2623: 2622: 2612: 2607: 2602: 2596: 2594: 2590: 2589: 2587: 2586: 2581: 2576: 2570: 2565: 2560: 2555: 2550: 2545: 2540: 2535: 2530: 2525: 2523:Interconnector 2520: 2515: 2510: 2505: 2500: 2495: 2490: 2485: 2480: 2475: 2473:Dynamic demand 2470: 2465: 2459: 2457: 2447: 2444: 2443: 2441: 2440: 2435: 2430: 2425: 2420: 2415: 2410: 2405: 2403:Combined cycle 2400: 2395: 2389: 2387: 2381: 2380: 2377: 2376: 2374: 2373: 2368: 2363: 2358: 2357: 2356: 2351: 2346: 2341: 2336: 2326: 2321: 2316: 2311: 2306: 2300: 2298: 2292: 2291: 2289: 2288: 2283: 2282: 2281: 2276: 2271: 2266: 2255: 2253: 2244: 2240: 2239: 2232: 2230: 2228: 2227: 2222: 2217: 2212: 2207: 2202: 2197: 2192: 2187: 2182: 2180:Load-following 2177: 2172: 2167: 2162: 2157: 2152: 2147: 2142: 2137: 2135:Electric power 2132: 2127: 2122: 2117: 2112: 2106: 2104: 2100: 2099: 2092: 2091: 2084: 2077: 2069: 2063: 2062: 2056: 2043: 2037: 2022: 2019: 2016: 2015: 2003: 1991: 1979: 1967: 1958:, p. 322. 1945: 1936:, p. 321. 1926: 1914: 1902: 1890: 1875: 1863: 1851: 1842:, p. 329. 1832: 1817: 1808:, p. 368. 1798: 1789:, p. 361. 1779: 1770:, p. 365. 1760: 1751:, p. 363. 1734: 1706: 1682: 1667: 1655: 1643: 1631: 1619: 1600: 1581: 1569: 1560:, p. 313. 1545: 1533: 1521: 1509: 1497: 1485: 1473: 1458: 1446: 1422: 1399: 1390:, p. 422. 1380: 1371:, p. 375. 1361: 1349: 1319: 1293: 1271: 1236: 1221: 1202: 1190: 1181:, p. 342. 1171: 1162:, p. 341. 1152: 1143:, p. 335. 1133: 1124:, p. 334. 1114: 1087: 1060: 1059: 1057: 1054: 1034:microprocessor 1009:Main article: 1006: 1003: 997: 994: 984: 981: 975: 972: 936: 933: 925: 924: 920: 914: 908: 904: 900: 896: 892: 885: 863: 860: 805:short circuits 796: 793: 762: 759: 730:) is minimal. 714:and switching 677: 674: 649: 646: 613:substation in 602: 599: 574: 571: 559:direct current 547:Main article: 544: 541: 536: 535: 528: 513: 512: 509: 502: 500: 497: 490: 488: 482:Switchyard at 481: 474: 448: 445: 428: 425: 380: 377: 360:distribution. 332: 329: 264: 261: 260: 259: 256:direct current 248: 241: 235: 230:for efficient 195: 192: 179: 176: 81: 80: 77: 76:Security fence 74: 71: 68: 65: 62: 59: 56: 53: 52:Overhead lines 50: 47: 43: 41: 40: 37: 33: 15: 9: 6: 4: 3: 2: 2851: 2840: 2837: 2836: 2834: 2819: 2811: 2810: 2807: 2801: 2798: 2796: 2793: 2792: 2790: 2782: 2776: 2773: 2771: 2768: 2766: 2763: 2761: 2758: 2756: 2755:Pigouvian tax 2753: 2751: 2748: 2746: 2743: 2741: 2738: 2736: 2733: 2731: 2728: 2726: 2723: 2721: 2718: 2716: 2713: 2711: 2708: 2706: 2703: 2702: 2700: 2692: 2685: 2682: 2680: 2677: 2675: 2672: 2670: 2667: 2665: 2662: 2658: 2655: 2653: 2652:Earth-leakage 2650: 2649: 2648: 2645: 2643: 2640: 2639: 2637: 2629: 2621: 2618: 2617: 2616: 2613: 2611: 2608: 2606: 2603: 2601: 2598: 2597: 2595: 2593:Failure modes 2591: 2585: 2582: 2580: 2577: 2574: 2571: 2569: 2566: 2564: 2561: 2559: 2556: 2554: 2551: 2549: 2546: 2544: 2543:Power station 2541: 2539: 2536: 2534: 2531: 2529: 2526: 2524: 2521: 2519: 2516: 2514: 2511: 2509: 2506: 2504: 2501: 2499: 2496: 2494: 2491: 2489: 2486: 2484: 2481: 2479: 2476: 2474: 2471: 2469: 2466: 2464: 2461: 2460: 2458: 2455: 2450: 2445: 2439: 2436: 2434: 2431: 2429: 2428:Rankine cycle 2426: 2424: 2421: 2419: 2416: 2414: 2411: 2409: 2408:Cooling tower 2406: 2404: 2401: 2399: 2396: 2394: 2391: 2390: 2388: 2386: 2382: 2372: 2369: 2367: 2364: 2362: 2359: 2355: 2352: 2350: 2347: 2345: 2342: 2340: 2337: 2335: 2332: 2331: 2330: 2327: 2325: 2322: 2320: 2317: 2315: 2312: 2310: 2307: 2305: 2302: 2301: 2299: 2297: 2293: 2287: 2284: 2280: 2277: 2275: 2272: 2270: 2267: 2265: 2262: 2261: 2260: 2257: 2256: 2254: 2252: 2251:Non-renewable 2248: 2245: 2241: 2236: 2226: 2223: 2221: 2218: 2216: 2213: 2211: 2208: 2206: 2203: 2201: 2198: 2196: 2193: 2191: 2188: 2186: 2183: 2181: 2178: 2176: 2173: 2171: 2170:Grid strength 2168: 2166: 2163: 2161: 2158: 2156: 2153: 2151: 2148: 2146: 2143: 2141: 2138: 2136: 2133: 2131: 2128: 2126: 2125:Demand factor 2123: 2121: 2118: 2116: 2113: 2111: 2108: 2107: 2105: 2101: 2097: 2090: 2085: 2083: 2078: 2076: 2071: 2070: 2067: 2059: 2053: 2049: 2044: 2040: 2034: 2030: 2025: 2024: 2013:, p. 89. 2012: 2007: 2001:, p. 88. 2000: 1995: 1989:, p. 63. 1988: 1983: 1977:, p. 62. 1976: 1971: 1963: 1957: 1952: 1950: 1941: 1935: 1930: 1924:, p. 77. 1923: 1918: 1911: 1906: 1900:, p. 76. 1899: 1894: 1888:, p. 83. 1887: 1882: 1880: 1873:, p. 74. 1872: 1867: 1861:, p. 71. 1860: 1855: 1847: 1841: 1836: 1830:, p. 72. 1829: 1824: 1822: 1813: 1807: 1806:Glaubitz 2018 1802: 1794: 1788: 1787:Glaubitz 2018 1783: 1775: 1769: 1768:Glaubitz 2018 1764: 1756: 1750: 1749:Glaubitz 2018 1745: 1743: 1741: 1739: 1730: 1725:, p. 13. 1724: 1719: 1717: 1715: 1713: 1711: 1702: 1697:, p. 12. 1696: 1691: 1689: 1687: 1680:, p. 70. 1679: 1674: 1672: 1665:, p. 69. 1664: 1659: 1653:, p. 81. 1652: 1647: 1641:, p. 65. 1640: 1635: 1629:, p. 64. 1628: 1623: 1615: 1609: 1604: 1596: 1590: 1585: 1579:, p. 56. 1578: 1573: 1565: 1559: 1554: 1552: 1550: 1542: 1537: 1531:, p. 54. 1530: 1525: 1519:, p. 51. 1518: 1513: 1506: 1501: 1494: 1489: 1482: 1477: 1471:, p. 42. 1470: 1465: 1463: 1456:, p. 41. 1455: 1450: 1444: 1440: 1439:0-07-020974-X 1436: 1432: 1426: 1419: 1415: 1414: 1409: 1403: 1395: 1389: 1384: 1376: 1370: 1365: 1359:, p. 68. 1358: 1353: 1337: 1330: 1323: 1307: 1303: 1297: 1282: 1275: 1259: 1252: 1245: 1243: 1241: 1234:, p. 54. 1233: 1228: 1226: 1218: 1213: 1211: 1209: 1207: 1199: 1194: 1186: 1180: 1175: 1167: 1161: 1156: 1148: 1142: 1137: 1129: 1123: 1118: 1103:. Los Angeles 1102: 1098: 1091: 1075: 1071: 1065: 1061: 1053: 1051: 1047: 1043: 1039: 1035: 1031: 1027: 1023: 1019: 1012: 1002: 993: 989: 980: 974:Control rooms 971: 969: 965: 961: 960:wind turbines 957: 953: 949: 948:reactive load 945: 941: 932: 929: 923:construction. 921: 918: 915: 912: 909: 890: 886: 883: 878: 877: 876: 874: 869: 866:High-voltage 859: 856: 851: 849: 843: 841: 836: 832: 830: 826: 822: 818: 814: 810: 806: 802: 792: 789: 785: 780: 776: 771: 769: 754: 750: 746: 744: 740: 736: 731: 729: 725: 721: 717: 713: 709: 704: 702: 698: 693: 691: 682: 673: 671: 667: 662: 658: 656: 645: 642: 635: 628: 623: 616: 612: 607: 598: 596: 592: 588: 584: 580: 570: 568: 564: 560: 556: 550: 540: 533: 529: 526: 522: 521: 520: 518: 506: 501: 494: 489: 485: 478: 473: 472: 471: 469: 464: 462: 461:power station 457: 455: 444: 442: 438: 434: 424: 422: 418: 414: 409: 407: 402: 398: 397:wind turbines 394: 390: 386: 376: 372: 370: 365: 361: 358: 350: 345: 337: 328: 326: 322: 318: 314: 310: 306: 297: 293: 291: 287: 283: 279: 275: 270: 257: 253: 249: 246: 242: 239: 236: 233: 229: 225: 224: 223: 216: 209: 205: 200: 191: 189: 185: 171: 167: 165: 164:power station 161: 157: 152: 150: 145: 142: 137: 133: 129: 125: 121: 113: 108: 101: 97: 93: 88: 78: 75: 72: 69: 66: 63: 60: 57: 54: 51: 48: 45: 44: 38: 35: 34: 32: 28: 22: 2750:Net metering 2697:and policies 2615:Power outage 2584:Utility pole 2548:Pumped hydro 2454:distribution 2449:Transmission 2398:Cogeneration 2200:Power factor 2047: 2028: 2006: 1994: 1982: 1970: 1929: 1917: 1905: 1893: 1866: 1854: 1835: 1801: 1782: 1763: 1658: 1646: 1634: 1622: 1603: 1584: 1572: 1536: 1524: 1512: 1500: 1488: 1476: 1449: 1442: 1430: 1425: 1418:Utility Week 1417: 1411: 1402: 1383: 1364: 1352: 1340:. Retrieved 1335: 1322: 1310:. Retrieved 1305: 1296: 1284:. Retrieved 1274: 1262:. Retrieved 1257: 1219:, p. 7. 1193: 1174: 1155: 1136: 1117: 1105:. Retrieved 1101:The Guardian 1100: 1090: 1078:. Retrieved 1073: 1064: 1014: 999: 990: 986: 983:Transformers 977: 964:voltage drop 938: 926: 865: 854: 852: 844: 837: 833: 798: 772: 764: 747: 732: 705: 694: 687: 663: 659: 651: 643: 640: 615:Old Montreal 583:semi-trailer 578: 576: 552: 537: 514: 465: 458: 450: 430: 410: 382: 373: 366: 362: 356: 354: 302: 274:transformers 268: 266: 245:distribution 232:transmission 221: 181: 178:Construction 155: 153: 146: 141:transformers 132:distribution 128:transmission 119: 117: 30: 2745:Load factor 2600:Black start 2568:Transformer 2269:Natural gas 2220:Variability 2195:Peak demand 2185:Merit order 2115:Backfeeding 2048:Substations 1723:Twomey 2018 1695:Twomey 2018 1441:Chapter 17 1286:14 December 1107:10 December 1026:fiber optic 996:Maintenance 911:Mineral oil 817:power plant 743:three-phase 49:Ground wire 2787:production 2632:Protective 2563:Super grid 2558:Smart grid 2385:Generation 2319:Geothermal 2210:Repowering 2011:Blume 2016 1999:Blume 2016 1910:Blume 2016 1886:Blume 2016 1871:Blume 2016 1859:Blume 2016 1828:Blume 2016 1678:Blume 2016 1663:Blume 2016 1651:Blume 2016 1342:11 October 1312:4 February 1264:4 February 1232:Blume 2016 1179:Okada 2018 1160:Okada 2018 1141:Okada 2018 1122:Okada 2018 1080:4 February 1056:References 1050:smart grid 1005:Automation 935:Capacitors 862:Switchgear 821:capacitors 795:Components 720:insulation 718:can cause 555:rectifiers 413:Brauweiler 307:plus some 184:contractor 156:substation 124:generation 120:substation 2695:Economics 2418:Micro CHP 2296:Renewable 2279:Petroleum 2274:Oil shale 2160:Grid code 2120:Base load 1987:Finn 2019 1975:Finn 2019 1922:Finn 2019 1898:Finn 2019 1639:Finn 2019 1627:Finn 2019 1577:Finn 2019 1541:Finn 2019 1529:Finn 2019 1517:Finn 2019 1505:Finn 2019 1493:Finn 2019 1481:Finn 2019 1469:Finn 2019 1454:Finn 2019 1357:Finn 2019 1217:Finn 2019 1198:Finn 2019 1042:IEC 61850 940:Capacitor 928:Reclosers 873:power arc 788:marconite 784:bentonite 775:grounding 768:flashover 712:lightning 468:switching 401:inverters 389:wind farm 210:, Finland 154:The word 96:Australia 92:Melbourne 2833:Category 2818:Category 2605:Brownout 2393:AC power 2103:Concepts 1306:metacafe 829:reactors 655:drainage 543:Railways 254:(AC) to 2634:devices 2344:Thermal 2339:Osmotic 2334:Current 2314:Biomass 2304:Biofuel 2286:Nuclear 2243:Sources 840:busbars 739:busbars 728:outages 421:lignite 349:Toronto 136:voltage 2329:Marine 2309:Biogas 2054:  2035:  1437:  1074:Jemena 1046:Modbus 917:Vacuum 827:, and 761:Safety 716:surges 629:river. 601:Design 417:Hradec 317:relays 204:Kaanaa 130:, and 2686:(GFI) 2575:(TSO) 2361:Solar 2349:Tidal 2324:Hydro 1332:(PDF) 1254:(PDF) 958:, or 813:fuses 735:buses 706:With 666:lease 587:truck 532:tower 517:fault 321:SCADA 194:Types 149:SCADA 2452:and 2371:Wind 2354:Wave 2264:Coal 2052:ISBN 2033:ISBN 1962:help 1940:help 1846:help 1812:help 1793:help 1774:help 1755:help 1729:help 1701:help 1614:help 1595:help 1564:help 1435:ISBN 1394:help 1375:help 1344:2017 1314:2016 1288:2013 1266:2016 1185:help 1166:help 1147:help 1128:help 1109:2022 1082:2016 1044:and 1038:DNP3 627:Bóbr 557:for 433:HVDC 319:and 258:(DC) 208:Pori 160:grid 891:(SF 811:or 786:or 595:war 593:or 525:arc 399:or 391:or 383:In 305:bus 2835:: 1948:^ 1878:^ 1820:^ 1737:^ 1709:^ 1685:^ 1670:^ 1548:^ 1461:^ 1410:, 1334:. 1304:. 1256:. 1239:^ 1224:^ 1205:^ 1099:. 1072:. 1052:. 1040:, 1024:, 1020:, 853:A 823:, 672:. 577:A 530:a 355:A 327:. 315:, 267:A 206:, 126:, 118:A 94:, 2088:e 2081:t 2074:v 2060:. 2041:. 1964:) 1942:) 1848:) 1814:) 1795:) 1776:) 1757:) 1731:) 1703:) 1616:) 1597:) 1566:) 1396:) 1377:) 1346:. 1316:. 1290:. 1268:. 1187:) 1168:) 1149:) 1130:) 1111:. 1084:. 905:6 901:6 897:6 893:6 527:, 280:/ 23:.

Index

Substation (disambiguation)


Melbourne
Australia
high-voltage transformer fire barriers

Warren, Minnesota
generation
transmission
distribution
voltage
transformers
SCADA
grid
power station

contractor
electrical utility

Kaanaa
Pori

electric power generation
transmission
Interconnection
distribution
alternating current
direct current
transformers

Text is available under the Creative Commons Attribution-ShareAlike License. Additional terms may apply.