Knowledge

Power cable

Source ๐Ÿ“

235:
materials for a transit application may be specified not to produce large amounts of smoke if burned (low smoke zero halogen). Cables intended for direct burial must consider damage from backfill or dig-ins. HDPE or polypropylene jackets are common for this use. Cables intended for subway (underground vaults) may consider oil, fire resistance, or low smoke as a priority. Few cables these days still employ an overall lead sheath. However, some utilities may still install paper insulated lead covered cable in distribution circuits. Transmission or submarine cables are more likely to use lead sheaths. However, lead is in decline and few manufacturers exist today to produce such items. When cables must run where exposed to mechanical damage (industrial sites), they may be protected with flexible steel tape or wire armor, which may also be covered by a water-resistant jacket.
278: 223:). The cable may include uninsulated conductors used for the circuit neutral or for ground (earth) connection. The grounding conductor connects the equipment's enclosure/chassis to ground for protection from electric shock. These uninsulated versions are known are bare conductors or tinned bare conductors. The overall assembly may be round or flat. Non-conducting filler strands may be added to the assembly to maintain its shape. Filler materials can be made in non-hydroscopic versions if required for the application. 383:
generally stranding class A, B, or C. These classes allow for the cable to be trained into a final installed position where the cable will generally not be disturbed. Class A, B, and C offer more durability, especially when pulling cable, and are generally cheaper. Power utilities generally order Class B stranded wire for primary and secondary voltage applications. At times, a solid conductor medium voltage cable can be used when flexibility is not a concern but low cost and water blocking are prioritized.
65: 316: 231:. The armor wires are attached to supporting plates periodically to help support the weight of the cable. A supporting plate may be included on each floor of the building, tower, or structure. This cable would be called an armored riser cable. For shorter vertical transitions (perhaps 30โ€“150 feet) an unarmored cable can be used in conjunction with basket (Kellum) grips or even specially designed duct plugs. 203:
and cable trays, which may contain one or more conductors. When it is intended to be used inside a building, nonmetallic sheathed building cable (NM-B) consists of two or more wire conductors (plus a grounding conductor) enclosed inside a thermoplastic insulation sheath that is heat-resistant. It has
256:
For circuits operating at or above 2,000 volts between conductors, a conductive shield should surround the conductor's insulation. This equalizes electrical stress on the cable insulation. This technique was patented by Martin Hochstadter in 1916; the shield is sometimes called a Hochstadter shield.
198:
Cables for direct burial or for exposed installations may also include metal armor in the form of wires spiraled around the cable, or a corrugated tape wrapped around it. The armor may be made of steel or aluminum, and although connected to earth ground is not intended to carry current during normal
386:
Applications requiring a cable to be moved repeatedly, such as for portable equipment, more flexible cables called "cords" or "flex" are used (stranding class G-M). Flexible cords contain fine stranded conductors, rope lay or bunch stranded. They feature overall jackets with appropriate amounts of
226:
Special purpose power cables for overhead applications are often bound to a high strength alloy, ACSR, or alumoweld messenger. This cable is called aerial cable or pre-assembled aerial cable (PAC). PAC can be ordered unjacketed, however, this is less common in recent years due to the low added cost
286:
Liquid filled cables are known for extremely long service lives with little to no outages. Unfortunately, oil leaks into soil and bodies of water are of grave concern and maintaining a fleet of the needed pumping stations is a drain on the O+M budget of most power utilities. Pipe type cables are
260:
To drain off stray voltage, a metallic shield will be placed over the "semicon." This shield is intended to "make safe" the cable by pulling the voltage on the outside of the insulation down to zero (or at least under the OSHA limit of 50 volts). This metallic shield can consist of a thin copper
257:
Aside from the semi conductive ("semicon") insulation shield, there will also be a conductor shield. The conductor shield may be semi conductive (usually) or non conducting. The purpose of the conductor shield is similar to the insulation shield: it is a void filler and voltage stress equalizer.
269:
Liquid or gas filled cables are still employed in distribution and transmission systems today. Cables of 10 kV or higher may be insulated with oil and paper, and are run in a rigid steel pipe, semi-rigid aluminum or lead sheath. For higher voltages the oil may be kept under pressure to prevent
382:
All electrical cables are somewhat flexible, allowing them to be shipped to installation sites wound on reels, drums or hand coils. Flexibility is an important factor in determining the appropriate stranding class of the cable as it directly affects the minimum bending radius. Power cables are
265:
would be dangerous. Multi-point grounding is the most common way to ground the cable's shield. Some special applications require shield breaks to limit circulating currents during the normal operations of the circuit. Circuits with shield breaks could be single or multi point grounded. Special
234:
Material specification for the cable's jacket will often consider resistance to water, oil, sunlight, underground conditions, chemical vapors, impact, fire, or high temperatures. In nuclear industry applications the cable may have special requirements for ionizing radiation resistance. Cable
261:
tape, concentric drain wires, flat straps, lead sheath, or other designs. The metallic shields of a cable are connected to earth ground at the ends of the cable, and possibly locations along the length if voltage rise during
183:
Cables consist of three major components: conductors, insulation, protective jacket. The makeup of individual cables varies according to application. The construction and material are determined by three main factors:
281:
A high-voltage cable designed for 400 kV. The large conductor in the center carries the current, smaller conductors on the outside act as a shield to equalize the voltage stress in the thick polyethylene insulation
148:
Aluminum wire was used in the 1960s and 1970s as a cheap replacement for copper and is still used today, but this is now considered unsafe, without proper installation, due to corrosion, softness and creeping of
180:
Modern power cables come in a variety of sizes, materials, and types, each particularly adapted to its uses. Large single insulated conductors are also sometimes called power cables in the industry.
135:
Armored cable, known by the genericized trademark "BX" - flexible steel sheath with two cloth-covered, rubber-insulated conductors - introduced in 1906 but more expensive than open single conductors
57:
within buildings, buried in the ground, run overhead, or exposed. Power cables that are bundled inside thermoplastic sheathing and that are intended to be run inside a building are known as
100:
in 1844, it was not applied to cable insulation until the 1880s, when it was used for lighting circuits. Rubber-insulated cable was used for 11,000-volt circuits in 1897 installed for the
194:
Environmental conditions such as temperature, water, chemical or sunlight exposure, and mechanical impact, determining the form and composition of the outer cable jacket.
468: 391: 488: 599: 387:
filler materials to improve their flexibility, trainability, and durability. Heavy duty flexible power cords such as those feeding a
624: 138:
Rubber-insulated wires with jackets of woven cotton cloth (usually impregnated with tar), waxed paper filler - introduced in 1922
227:
of supplying a polymeric jacket. For vertical applications the cable may include armor wires on top of the jacket, steel or
204:
advantages over armored building cable because it is lighter, easier to handle, and its sheathing is easier to work with.
394:
are carefully engineered โ€” their life is measured in weeks. Very flexible power cables are used in automated machinery,
637:
Terrell Croft and Wilford Summers (ed), American Electricans' Handbook, Eleventh Edition, McGraw Hill, New York (1987)
287:
often converted to solid insulation circuit at the end of their service life despite a shorter expected service life.
662: 642: 583: 529: 363: 345: 657:
and H. Wayne Beaty, Standard Handbook for Electrical Engineers, Eleventh Edition, McGraw-Hill, New York, 1978,
600:"10 Wiring Problems Solved | Electrical | Plumbing, HVAC & Electrical | This Old House - 12" 493: 483: 341: 17: 337: 142: 675: 708: 435: 552: 462: 452: 262: 122:
Typical residential and office construction in North America has gone through several technologies:
326: 107:
Mass-impregnated paper-insulated medium voltage cables were commercially practical by 1895. During
330: 156: 603: 703: 218: 208: 129: 46: 8: 473: 440: 215:
conductors, although small power cables may use solid conductors in sizes of up to 1/0. (
49:, usually held together with an overall sheath. The assembly is used for transmission of 406:
for further description of flexible power cables. Other types of flexible cable include
422: 299: 291: 277: 251: 200: 658: 638: 579: 556: 525: 271: 170: 159:
in some cloth wires from the 1920s to 1970s, but discontinued due to its health risk.
54: 191:
Current-carrying capacity, determining the cross-sectional size of the conductor(s);
457: 112: 97: 42: 298:
for insulation. They require special techniques for jointing and terminating, see
199:
operation. Electrical power cables are sometimes installed in raceways, including
76:
Flexible power cables are used for portable devices, mobile tools, and machinery.
403: 377: 50: 654: 415: 238:
A hybrid cable can include conductors for control signals or may also include
697: 478: 411: 101: 85: 30:
This article is about electric power conductors. For portable equipment, see
560: 498: 407: 239: 116: 108: 399: 162: 132:, 1880sโ€“1930s, using asphalt-saturated cloth or later rubber insulation 93: 31: 617: 388: 64: 449:โ€“ for a description of current carrying capacity of wires and cables 315: 446: 395: 212: 152: 228: 89: 92:
rods, wrapped in jute and placed in rigid pipes filled with a
188:
Working voltage, determining the thickness of the insulation;
69: 295: 305: 96:
compound. Although vulcanized rubber had been patented by
501:โ€“ another consideration when selecting proper cable sizes 126:
Early bare and cloth-covered wires installed with staples
543: 541: 625:"The True Story Behind Aluminum Wiring โ€“ Part One" 538: 266:engineering situations may require cross bonding. 469:Industrial and multiphase power plugs and sockets 217:For a detailed discussion on copper cables, see: 84:The first power distribution system developed by 695: 592: 145:(e.g., NM-B), produced by such brands as Romex 294:use polyethylene or other polymers, including 519: 489:Restriction of Hazardous Substances Directive 421:An X-ray cable is a special type of flexible 53:. Power cables may be installed as permanent 27:Bundle of wires for transmitting electricity 573: 344:. Unsourced material may be challenged and 364:Learn how and when to remove this message 576:The History of Electric Wires and Cables 276: 63: 45:, an assembly of one or more electrical 306:Flexibility of cables (stranding class) 61:(nonmetallic sheathed building cable). 14: 696: 443:โ€“ for a table of cross section sizes 342:adding citations to reliable sources 309: 270:formation of voids that would allow 119:insulation were applied to cables. 24: 549:Underground Systems Reference Book 245: 25: 720: 378:Wire ยง Solid versus stranded 314: 141:Modern two or three-wire+ground 175: 668: 648: 631: 567: 513: 494:Telecommunications power cable 484:Railway electrification system 165:, a PVC-sheathed armored cable 88:in 1882 in New York City used 13: 1: 522:Undergrounding electric lines 506: 274:within the cable insulation. 676:"Nonmetallic Building Cable" 645:, sections 2-13 through 2-84 7: 578:. Peter Pergrinus, London. 428: 418:, and communication cable. 10: 725: 436:AC power plugs and sockets 375: 249: 207:Power cables use stranded 168: 79: 29: 553:Edison Electric Institute 463:Ethylene propylene rubber 453:Cross-linked polyethylene 398:, and machine tools. See 520:A. J. Pansini (1978). 283: 73: 280: 219:Copper wire and cable 169:Further information: 111:several varieties of 67: 574:R. M. Black (1983). 338:improve this section 157:electrical insulator 130:Knob and tube wiring 474:Overhead power line 441:American wire gauge 292:high-voltage cables 143:PVC-insulated cable 423:high-voltage cable 300:High-voltage cable 284: 272:partial discharges 252:High-voltage cable 201:electrical conduit 74: 709:Electrical wiring 374: 373: 366: 171:Electrical wiring 16:(Redirected from 716: 688: 687: 685: 683: 672: 666: 652: 646: 635: 629: 628: 627:. 21 March 2015. 621: 615: 614: 612: 611: 602:. Archived from 596: 590: 589: 571: 565: 564: 545: 536: 535: 517: 458:Electrical cable 369: 362: 358: 355: 349: 318: 310: 113:synthetic rubber 98:Charles Goodyear 51:electrical power 43:electrical cable 21: 724: 723: 719: 718: 717: 715: 714: 713: 694: 693: 692: 691: 681: 679: 674: 673: 669: 653: 649: 636: 632: 623: 622: 618: 609: 607: 598: 597: 593: 586: 572: 568: 547: 546: 539: 532: 518: 514: 509: 504: 431: 404:extension cable 392:cutting machine 380: 370: 359: 353: 350: 335: 319: 308: 254: 248: 246:Higher voltages 178: 173: 155:was used as an 104:power project. 82: 35: 28: 23: 22: 15: 12: 11: 5: 722: 712: 711: 706: 690: 689: 667: 655:Donald G. Fink 647: 630: 616: 591: 584: 566: 537: 530: 511: 510: 508: 505: 503: 502: 496: 491: 486: 481: 476: 471: 466: 460: 455: 450: 444: 438: 432: 430: 427: 410:, extensible, 376:Main article: 372: 371: 322: 320: 313: 307: 304: 250:Main article: 247: 244: 240:optical fibers 196: 195: 192: 189: 177: 174: 167: 166: 160: 150: 146: 139: 136: 133: 127: 81: 78: 26: 9: 6: 4: 3: 2: 721: 710: 707: 705: 702: 701: 699: 677: 671: 664: 663:0-07-020974-X 660: 656: 651: 644: 643:0-07-013932-6 640: 634: 626: 620: 606:on 2014-10-06 605: 601: 595: 587: 585:0-86341-001-4 581: 577: 570: 562: 558: 554: 550: 544: 542: 533: 531:0-8104-0827-9 527: 523: 516: 512: 500: 497: 495: 492: 490: 487: 485: 482: 480: 479:Portable cord 477: 475: 472: 470: 467: 464: 461: 459: 456: 454: 451: 448: 445: 442: 439: 437: 434: 433: 426: 424: 419: 417: 413: 409: 405: 401: 397: 393: 390: 384: 379: 368: 365: 357: 347: 343: 339: 333: 332: 328: 323:This section 321: 317: 312: 311: 303: 301: 297: 293: 288: 279: 275: 273: 267: 264: 258: 253: 243: 241: 236: 232: 230: 224: 222: 220: 214: 210: 205: 202: 193: 190: 187: 186: 185: 181: 172: 164: 161: 158: 154: 151: 147: 144: 140: 137: 134: 131: 128: 125: 124: 123: 120: 118: 114: 110: 105: 103: 102:Niagara Falls 99: 95: 91: 87: 86:Thomas Edison 77: 71: 66: 62: 60: 56: 52: 48: 44: 40: 33: 19: 18:Power cabling 704:Power cables 682:11 September 680:. Retrieved 670: 650: 633: 619: 608:. Retrieved 604:the original 594: 575: 569: 548: 521: 515: 499:Voltage drop 420: 408:twisted pair 385: 381: 360: 351: 336:Please help 324: 289: 285: 268: 259: 255: 237: 233: 225: 216: 206: 197: 182: 179: 176:Construction 121: 117:polyethylene 109:World War II 106: 83: 75: 72:power cable. 58: 38: 36: 149:connection. 39:power cable 698:Categories 610:2014-10-03 507:References 400:power cord 354:April 2024 242:for data. 163:Teck cable 94:bituminous 47:conductors 32:power cord 678:. Granger 665:pg. 18-85 389:mine face 325:does not 555:. 1957. 447:Ampacity 429:See also 416:shielded 396:robotics 213:aluminum 153:Asbestos 561:1203459 412:coaxial 346:removed 331:sources 290:Modern 80:History 661:  641:  582:  559:  528:  282:layer. 263:faults 229:Kevlar 209:copper 90:copper 55:wiring 41:is an 465:(EPR) 70:USB-C 684:2020 659:ISBN 639:ISBN 580:ISBN 557:OCLC 526:ISBN 402:and 329:any 327:cite 296:XLPE 115:and 59:NM-B 340:by 211:or 700:: 551:. 540:^ 524:. 425:. 414:, 302:. 68:A 37:A 686:. 613:. 588:. 563:. 534:. 367:) 361:( 356:) 352:( 348:. 334:. 221:. 34:. 20:)

Index

Power cabling
power cord
electrical cable
conductors
electrical power
wiring

USB-C
Thomas Edison
copper
bituminous
Charles Goodyear
Niagara Falls
World War II
synthetic rubber
polyethylene
Knob and tube wiring
PVC-insulated cable
Asbestos
electrical insulator
Teck cable
Electrical wiring
electrical conduit
copper
aluminum
Copper wire and cable
Kevlar
optical fibers
High-voltage cable
faults

Text is available under the Creative Commons Attribution-ShareAlike License. Additional terms may apply.

โ†‘