Knowledge

Fire alarm system

Source 📝

536:
impracticable or undesirable. The signals from the speakers are used to direct the occupant's response. The fire alarm system automatically actuates speakers in a fire event. Following a pre-alert tone, selected groups of speakers may transmit one or more prerecorded messages directing the occupants to safety. These messages may be repeated in one or more languages. The system may be controlled from one or more locations within the building, known as "fire warden stations", or from a single location designated as the building's "fire command center". From these control locations, trained personnel activating and speaking into a dedicated microphone can suppress the replay of automated messages to initiate or relay real-time voice instructions.
1775: 578:
capabilities to support new requirements for mass notification. These expanded capabilities include support for multiple types of emergency messaging (i.e., inclement weather emergency, security alerts, amber alerts). The major requirement of a mass notification system is to provide prioritized messaging according to the local facilities' emergency response plan, and the fire alarm system must support the promotion and demotion of notifications based on this emergency response plan. In the United States,
142: 2444: 515:) to alert the occupants of the need to evacuate or take action in the event of a fire or other emergency. Evacuation signals may consist of simple appliances that transmit uncoded information, coded appliances that transmit a predetermined pattern, and/or appliances that transmit audible and visible information such as live or prerecorded instructions and illuminated message displays. Some notification appliances are a combination of fire alarm and general 500: 312: 560:, 18.4.2 (2010 Edition), Temporal Code 3 is the standard audible notification in a modern system. It consists of a repeated three-pulse cycle (0.5 s on, 0.5 s off, 0.5 s on, 0.5 s off, 0.5 s on, 1.5 s off). Voice evacuation is the second most common audible notification in modern systems. Legacy systems, typically found in older schools and buildings, have used continuous tones alongside other audible notifications. 647: 304: 45: 492: 154: 428: 2456: 711: 508:
different tones, either low, medium, or high, depending on the country and manufacturer of the device. Most fire alarm systems in Europe sound like a siren with alternating frequencies. Fire alarm electronic devices are known as horns in the United States and Canada and can be continuous or set to different codes. Fire alarm warning devices can also be set to different volume levels.
206:
components, arrangements, and interfaces necessary to accomplish these requirements. Equipment specifically manufactured for these purposes is selected, and standardized installation methods are anticipated during the design. There are several commonly referenced standards for fire protection requirements, including:
810:. There are many types of fire alarm systems, each suited to different building types and applications. A fire alarm system can vary dramatically in price and complexity, from a single panel with a detector and sounder in a small commercial property to an addressable fire alarm system in a multi-occupancy building. 779:
level—used when the fire alarm initiation occurred on the primary level), illumination of the "fire hat" indicator when an alarm occurs in the elevator hoistway or associated control room, and in some cases shunt trip (disconnect) of elevator power (generally used where the control room or hoistway is protected by
439:, manual pull stations, or simply pull stations, break glass stations, and (in Europe) call points, are installed to be readily located (usually near the exits of a floor or building), identified, and operated. They are usually actuated using physical interaction, such as pulling a lever or breaking glass. 881:
This category is designed to give early warnings to everyone. Detectors should be placed in all escape routes and all rooms that open onto escape routes. Category 3 systems provide more extensive cover than Category 4. The objective is to warn the occupants of the building early enough to ensure that
535:
Audible textual appliances can be employed as part of a fire alarm system that includes EVAC capabilities. High-reliability speakers notify the occupants of the need for action concerning a fire or other emergency. These speakers are employed in large facilities where general undirected evacuation is
845:
The system is installed throughout the building—the objective is to automatically call the fire brigade as early as possible to minimize any damage caused by the fire. Small low-risk areas can be excepted from the system, such as toilets and cupboards less than one square meter (11 sq ft).
205:
Fire alarm systems are designed after fire protection requirements in a location are established, which is usually done by referencing the minimum levels of security mandated by the appropriate model building code, insurance agencies, and other authorities. A fire alarm designer will detail specific
531:
systems (EVAC) to provide prerecorded and manual voice messages. Voice alarm systems are typically used in high-rise buildings, arenas, and other large "defend-in-place" occupancies such as hospitals and detention facilities where total evacuation is difficult to achieve. Voice-based systems allow
863:
A category L1 system is designed for the protection of life and which has automatic detectors installed throughout all areas of the building (including roof spaces and voids) to provide the earliest possible warning. A category L1 system is likely to be appropriate for the majority of residential
507:
Alarms can take many forms, but are most often either motorized bells or wall-mountable sounders or horns. They can also be speaker strobes that sound an alarm, followed by a voice evacuation message for clearer instructions on what to do. Fire alarm sounders can be set to certain frequencies and
329:
Remote annunciator: a device that connects directly to the panel; the annunciator's main purpose is to allow emergency personnel to view the system status and take command from outside the electrical room the panel is located in. Usually, annunciators are installed by the front door, the door the
872:
A category L2 system is designed for the protection of life and has automatic detectors installed in escape routes, rooms adjoining escape routes and high-hazard rooms. In medium-sized premises (sleeping no more than ten residents), category L2 system are often used. These fire alarm systems are
836:
Manual systems, e.g., handbells, gongs, etc. These may be purely manual or manual electric, the latter may have call points and sounders. They rely on the occupants of the building discovering the fire and acting to warn others by operating the system. Such systems form the basic requirement for
568:
In the United Kingdom, fire alarm evacuation signals generally consist of a two-tone siren with visual notifications in all public and common-use areas. Some fire alarm devices can emit an alert signal, which is generally used in schools for lesson changes, the start of morning break, the end of
890:
Category 4 systems cover escape routes and circulation areas only. Therefore, detectors will be placed in escape routes, although this may not be suitable depending on the risk assessment or if the size and complexity of a building are increased. Detectors might be located in other areas of the
778:
response teams and to ensure that cabs do not return to the floor of fire incidence, as well as preventing people from becoming trapped in the elevators. Phases of operation include primary recall (typically the ground level), alternate/secondary recall (typically a floor adjacent to the ground
739:
to allow automatic closure of the door on command from the fire control or upon failure of the power source, interconnection, or controlling element. Stored energy in the form of a spring or gravity can then close the door to restrict the passage of smoke from one space to another in order to
577:
New codes and standards introduced around 2010, especially the new UL Standard 2572, the US Department of Defense's UFC 4-021-01 Design and O&M Mass Notification Systems, and NFPA 72 2010 edition Chapter 24, have led fire alarm system manufacturers to expand their systems voice evacuation
854:
Detection should be provided in parts of the building where the risk of ignition is high and/or the contents are precious. Category 2 systems provide fire detection in specified parts of the building where there is either high risk or where business disruption must be minimized.
417:
Building safety interfaces: This interface allows the fire alarm system to control aspects of the built environment, prepare the building for fire, and control the spread of smoke fumes by influencing air movement, lighting, process control, human transport, and availability of
899:
This is the "all other situations" category, e.g., computer rooms, which may be protected with an extinguishing system triggered by automatic detection. Category 5 systems are the "custom" category and relate to special requirements that other categories cannot cover.
552:
In the United States, fire alarm evacuation signals generally consist of a standardized audible tone, with visual notification in all public and common-use areas. Emergency signals are intended to be distinct and understandable to avoid confusion with other signals.
1179: 235:
is a technical specification (CEN/TS) for fire detection and fire alarm systems (Part 14: Guidelines for planning, design, installation, commissioning, use, and maintenance). Technical Committee CEN/TC72 has prepared this document as part of the
792:
can be interfaced with a fire alarm system by adding a signaling control relay module to either the rack's power supply unit or the main amplifier driving the rack. The purpose of the fire alarm system interface is usually to "mute" the
543:
buildings, different evacuation messages may be played on each floor, depending on the location of the fire. The floor the fire is on along with ones above it may be told to evacuate while floors much lower may be asked to stand by.
1101: 481: 603:
Mass notification systems often extend the notification appliances of a standard fire alarm system to include PC-based workstations, text-based digital signage, and a variety of remote notification options including
632:
systems. In the United States, a residential fire alarm system is required in buildings where more than 12 smoke detectors are needed. Residential systems generally have fewer parts compared to commercial systems.
349:
is connected to the fire alarm system and its constituents in non-residential applications. "Dedicated branch circuits" should not be confused with "Individual branch circuits" which supply energy to a single
287:, the following standards outline the requirements, test methods, and performance criteria for fire detection control and indicating equipment utilised in building fire detection and fire alarm systems: 482: 244:
There are national codes in each European country for planning, design, installation, commissioning, use, and maintenance of fire detection systems with additional requirements that are mentioned on
213:, the international standard for the design, installation, commissioning, and service of fire detection and fire alarm systems in and around a building. This standard was published in August 2013. 1474: 181:, or other fire-related emergencies. Fire alarm systems are required in most commercial buildings. They may include smoke detectors, heat detectors, and manual fire alarm activation devices ( 873:
identical to an L3 system but with additional detection in areas with a high chance of ignition (e.g., kitchens) or where the risk to people is particularly increased (e.g., sleeping risk).
774:
operation are used for emergency elevator functions, such as the recall of associated elevator cab(s). The recall will cause the elevator cabs to return to the ground level for use by
442:
Automatically actuated devices can take many forms, and are intended to respond to any number of detectable physical changes associated with fire: convected thermal energy for a
1127: 1071: 361:, are used to supply energy during a primary power failure. The batteries can be either inside the bottom of the panel or inside a separate battery box installed near the panel. 864:
care premises. In practice, detectors should be placed in nearly all spaces and voids. With category 1 systems, the whole of a building is covered apart from minor exceptions.
1032:
ISO 7240-14:2013 | Fire detection and alarm systems — Part 14: Design, installation, commissioning and service of fire detection and fire alarm systems in and around buildings
1513: 2291: 483: 382:: This component uses energy supplied from the fire alarm system or other stored energy source to inform the proximate persons of the need to take action, usually to 1180:"Fire detection and fire alarm systems for buildings - Code of practice for design, installation, commissioning, and maintenance of systems in non-domestic premises" 466:
and computer algorithms to analyze and respond to the visible effects of fire and movement in applications inappropriate for or hostile to other detection methods.
326:(FACP), or fire alarm control unit (FACU): This component, the hub of the system, monitors inputs and system integrity, controls outputs, and transmits information. 744:
from a central controller connected to a fire panel, or acoustic, which learns the sound of the fire alarm and releases the door upon hearing this exact sound.
1299: 740:
facilitate evacuation and firefighting efforts. Electromagnetic fire door holders may also be hard-wired into the fire panel, radio-controlled, triggered by
1367:
Dunnings, A.; Breckon, T.P. (2018). "Experimentally Defined Convolutional Neural Network Architecture Variants for Non-temporal Real-time Fire Detection".
922:
Where addressable systems are in place, two faults should not remove protection from an area greater than 10,000 square meters (110,000 sq ft).
435:
Initiating devices used to activate a fire alarm system are either manually or automatically actuated devices. Manually actuated devices, also known as
931:
Stairwells, lift shafts or other vertical shafts (nonstop risers) within a single fire compartment should be considered as one or more separate zones.
2086: 761:
spaces. As part of the fire alarm system, these detectors may be connected to the fan motor control circuits in order to stop air movement, close
806:
In the United Kingdom, fire alarm systems in non-domestic premises are generally designed and installed in accordance with the guidance given in
1557: 271: 210: 2279: 265: 245: 232: 1894: 259: 253: 1079: 1584: 928:
Where the floor space exceeds 300 square meters (3,200 sq ft) then all zones should be restricted to a single floor level.
1612: 1298:
Chenebert, A.; Breckon, T.P.; Gaszczak, A. (September 2011). "A Non-temporal Texture Driven Approach to Real-time Fire Detection".
582:
also have requirements for visible notification in coordination with any audible notification activities to meet the needs of the
2258: 583: 911:
An important consideration when designing fire alarms is that of individual "zones". The following recommendations are found in
707:
Various equipment may be connected to a fire alarm system to facilitate evacuation or to control a fire, directly or indirectly:
189:. Fire alarm control panels are usually found in an electrical or panel room. Fire alarm systems generally use visual and audio 109: 1521: 938:
The NFPA recommends placing a list for reference near the fire alarm control panel showing the devices contained in each zone.
81: 1328: 1255:"AS AS 7240.2:2018 – Fire Detection and Alarm Systems Fire detection control and indicating equipment (ISO 7240-2:2017, MOD)" 1254: 2303: 2297: 1450: 1419: 1400: 1395:
National Fire Protection Association (February 2001). "Chapter 3 Fundamental Fire Protection Program and Design Elements".
1229: 1204: 957: 216: 731:
controlled by a fire alarm system or detection component that magnetically secures spring-loaded self-closing smoke-tight
88: 1799: 668: 62: 2482: 2174: 1458: 694: 475: 379: 158: 128: 925:
A building may be viewed as a single zone if the floor space is less than 300 square meters (3,200 sq ft).
676: 2459: 628:
Residential fire alarm systems are commonplace. Typically, residential fire alarm systems are installed along with
95: 1935: 1623: 532:
response personnel to conduct orderly evacuation and notify building occupants of changing event circumstances.
1342: 1280: 947: 672: 579: 66: 1368: 1230:"AS 4428.1998 – Fire detection, warning, control and intercom systems - Control and indicating equipment Fire" 77: 2285: 2242: 1914: 1577: 2403: 368:
to the fire alarm control unit and are manually or automatically activated. Examples include pull stations,
2487: 2356: 2194: 983: 182: 1397:
NFPA 805 Performance-Based Standard for Fire Protection for Light Water Reactor Electric Generating Plants
817:"M" manual systems (no automatic fire detectors, so the building is fitted with call points and sounders). 2227: 2159: 1976: 1809: 1153: 934:
The maximum distance traveled within a zone to locate the fire should not exceed 60 meters (200 ft).
31: 17: 169:
is a building system designed to detect, alert occupants, and alert emergency forces of the presence of
1794: 1734: 1005: 617: 2309: 2144: 1804: 1517: 2447: 2253: 2169: 2149: 2126: 1889: 1654: 1570: 657: 341:
Primary power supply: Commonly, a commercial power utility supplies a non-switched 120 or 240-volt
323: 224: 186: 146: 837:
places of employment with no sleeping risk; e.g., a fire cannot occur while occupants are asleep.
569:
morning break, the start of lunch break, the end of lunch break, and when the school day is over.
2096: 2061: 1909: 1859: 715: 661: 387: 55: 1205:"AS 1603.4-1987 – Automatic fire detection and alarm systems - Control and indicating equipment" 2237: 2116: 2091: 2081: 1789: 1749: 1488: 330:
fire department responds by, or in a fire command center. Annunciators typically have the same
102: 765:
and generally prevent the recirculation of toxic smoke and fumes from fire in occupied spaces.
749:
Duct-mounted smoke detectors may be mounted in such a manner as to sample the airflow through
519:
notification appliances, allowing both types of emergency notifications from a single device.
511:
Notification appliances utilize audible, visible, tactile, textual or even olfactory stimuli (
462:, and operation of sprinklers for a water-flow detector. Automatic initiating devices may use 223:, an established and widely used installation standard from the United States. In Canada, the 2424: 2398: 2351: 1966: 1854: 1834: 789: 354: 919:
A single zone should not exceed 2,000 square meters (22,000 sq ft) in floor space.
2121: 1981: 1689: 986:- a way to warn people through audible and visual devices when peoples lives are in danger. 383: 27:
A system, that works using multiple devices to warn of a fire or other types of emergencies
8: 2164: 2071: 952: 342: 331: 1951: 1879: 1844: 1839: 1694: 1334: 358: 2377: 2372: 2367: 2263: 2154: 2026: 1864: 1774: 1759: 1454: 1324: 459: 1338: 1046: 827:
Categories for automatic systems are further subdivided into L1 to L5 and P1 to P2.
596:
Tier 2 systems are out of the building and provide the middle level of survivability
2361: 1699: 1316: 1308: 794: 758: 395: 2056: 1991: 1930: 1899: 1874: 1824: 1819: 1633: 1593: 775: 178: 193:
to warn the occupants of the building. Some fire alarm systems may also disable
2222: 2199: 2184: 2046: 1986: 1956: 1925: 1869: 1829: 1764: 1754: 1649: 962: 912: 807: 780: 629: 609: 599:
Tier 3 systems are "At Your Side" and provide the lowest level of survivability
455: 451: 447: 436: 386:. This is done using a variety of audio and visual means, ranging from pulsing 373: 346: 277: 1312: 2476: 2429: 2419: 2217: 2189: 2106: 1724: 1714: 1684: 1628: 762: 736: 728: 593:
Tier 1 systems are in-building and provide the highest level of survivability
443: 403: 399: 369: 1547: 891:
building, but the objective of an L4 system is to protect the escape route.
141: 2346: 2232: 2111: 2101: 2036: 2001: 1961: 1920: 1884: 1674: 1669: 1639: 754: 391: 365: 1552: 1030: 2066: 2021: 2011: 1904: 1849: 1814: 1709: 1072:"VdS Guidelines for Planning and Installation of Fire Protection Systems" 972: 411: 2326: 2179: 1679: 1664: 1644: 967: 741: 311: 1297: 491: 2248: 2076: 2041: 2031: 2016: 1996: 1971: 1744: 1739: 1704: 1659: 1607: 1320: 516: 499: 303: 291: 1475:"What's the maximum amount of hardwired smoke alarms I can install?" 1435:. National Fire Alarm Association, 2009, Page 118, Subsection 24.4.1 1413: 1394: 646: 44: 2341: 2051: 2006: 1729: 1719: 1618: 771: 750: 724: 540: 512: 294:
AS 1603.4 (superseded), AS 4428.1 (superseded), and AS 7240.2:2018.
194: 1562: 1414:
National Fire Protection Association (2011). "Chapter 4 Annex A".
882:
all can exit the building before escape routes become impassable.
757:
fabricated explicitly for the transport of environmental air into
197:, which are unsafe to use during a fire under most circumstances. 557: 338:
screen, although some annunciators allow for full system control.
284: 240:
series of standards. This standard was published in October 2018.
427: 1433:
NFPA 72 – National Fire Alarm and Signaling Code – 2010 Edition
463: 190: 153: 823:"P" automatic systems intended for the protection of property. 522: 2382: 2336: 977: 605: 237: 174: 710: 185:). All components of a fire alarm system are connected to a 2331: 2292:
National Council of Examiners for Engineering and Surveying
732: 723:
Magnetic smoke door holders and retainers are wall-mounted
589:
Mass notification system categories include the following:
487:
The standard fire alarm sound used in most of North America
407: 319:
Fire alarm systems are composed of several distinct parts:
170: 820:"L" automatic systems intended for the protection of life. 1366: 613: 335: 1416:
NFPA 12 Standard on Carbon Dioxide Extinguishing Systems
801: 1403:. standard: Gaseous Fire Suppression Systems 3.10.7. 227:
or ULC provides fire system installation standards.
145:A fire alarm horn strobe, pull station, and remote 69:. Unsourced material may be challenged and removed. 1370:Proc. International Conference on Image Processing 1301:Proc. International Conference on Image Processing 1281:"The Components Of A Commercial Fire Alarm System" 813:BS 5839 Part 1 categorizes fire alarm systems as: 572: 2087:Penetrant (mechanical, electrical, or structural) 30:"Fire alarm" redirects here. For other uses, see 2474: 1553:Authoritative guide to fire alarm systems in UK 1291: 1360: 1578: 770:Automatic initiating devices associated with 636: 503:A fire alarm notification appliance in Sweden 161:as widely used under North American standards 1438: 364:Initiating devices: These components act as 1447:Fire Protection Handbook eighteenth edition 675:. Unsourced material may be challenged and 620:-based telephone text-to-speech messaging. 523:Emergency voice alarm communication systems 1895:Hypoxic air technology for fire prevention 1585: 1571: 1514:"Fire Industry Association Fact File 0058" 469: 353:Secondary (backup) power supplies: Sealed 2280:Fire Equipment Manufacturers' Association 695:Learn how and when to remove this message 149:connected together in a fire alarm system 129:Learn how and when to remove this message 1613:Boiling liquid expanding vapor explosion 1388: 709: 563: 498: 490: 479: 426: 310: 302: 152: 140: 2259:Listing and approval use and compliance 1407: 1278: 547: 14: 2475: 980:– European Standard for Fire detection 623: 357:or other emergency sources, including 2304:Society of Fire Protection Engineers 1566: 1518:the Fire Industry Association ("FIA") 1003: 422: 2455: 2298:National Fire Protection Association 1451:National Fire Protection Association 1444: 1420:National Fire Protection Association 1401:National Fire Protection Association 1006:"Lift safety in the event of a fire" 958:National Fire Protection Association 802:British fire alarm system categories 673:adding citations to reliable sources 640: 414:, or a combination of these devices. 334:as those available from the panel's 225:Underwriters' Laboratories of Canada 67:adding citations to reliable sources 38: 1592: 529:emergency voice alarm communication 315:Fire alarm speaker and pull station 24: 1800:Condensed aerosol fire suppression 1285:Commercial Fire And Communications 718:below a 10-inch (25 cm) bell. 25: 2499: 2175:Fire alarm notification appliance 1548:Section 283100 Fire Alarm Systems 1540: 1279:Mariani, Michael (8 April 2020). 1047:"CEN Community - List of members" 735:in the open position. The device 476:Fire alarm notification appliance 380:Fire alarm notification appliance 159:fire alarm notification appliance 2454: 2443: 2442: 1773: 645: 527:Some fire alarm systems utilize 43: 1936:Vehicle fire suppression system 1624:Combustibility and flammability 1506: 1481: 1467: 1426: 1272: 1247: 1222: 584:Americans with Disabilities Act 580:emergency communication systems 573:Emergency communication systems 446:, products of combustion for a 54:needs additional citations for 1445:Cote, Arthur E. (March 2000). 1197: 1172: 1146: 1120: 1094: 1064: 1039: 1023: 997: 948:Fire Safety Equivalency System 13: 1: 2286:Institution of Fire Engineers 2243:Fire Safety Evaluation System 1915:Personal protective equipment 1489:"Fire Door Holders - Geofire" 990: 495:A speaker with a remote light 2357:GHS precautionary statements 2195:Manual fire alarm activation 1307:. IEEE. pp. 1781–1784. 1004:Davis, Jemma (11 May 2018). 984:Emergency population warning 221:The National Fire Alarm Code 7: 2228:Fire protection engineering 2160:Explosive gas leak detector 1977:Electromagnetic door holder 1810:External water spray system 941: 355:lead-acid storage batteries 32:Fire alarm (disambiguation) 10: 2504: 2404:Harry C. Bigglestone Award 1795:Automatic fire suppression 1735:K-factor (fire protection) 637:Building safety interfaces 473: 307:A fire alarm control panel 29: 2438: 2412: 2391: 2319: 2310:Underwriters Laboratories 2272: 2208: 2145:Aspirating smoke detector 2135: 1944: 1805:Detonation flame arrester 1782: 1771: 1600: 1313:10.1109/ICIP.2011.6115796 906: 458:, combustion gases for a 200: 2483:Fire detection and alarm 2254:Kitchen exhaust cleaning 2170:Fire alarm control panel 2150:Carbon monoxide detector 2127:Standpipe (firefighting) 1890:Gaseous fire suppression 1655:Enthalpy of vaporization 1422:. standard: A.4.5.6.2.2. 797:in case of an emergency. 324:Fire alarm control panel 298: 187:fire alarm control panel 2097:Pressurisation ductwork 2062:Firewall (construction) 1910:Passive fire protection 1860:Fire suppression system 1259:infostore.saiglobal.com 1234:infostore.saiglobal.com 1209:infostore.saiglobal.com 1051:standards.cencenelec.eu 716:fire alarm pull station 470:Notification appliances 431:Fire alarm pull station 2273:Industry organizations 2238:Fire-resistance rating 2117:Smoke exhaust ductwork 2092:Penetration (firestop) 2082:Packing (firestopping) 1790:Active fire protection 1750:Spontaneous combustion 1546:Example Specification 719: 504: 496: 488: 432: 372:, duct detectors, and 316: 308: 162: 150: 2425:Template:Firefighting 2399:Arthur B. Guise Medal 2352:GHS hazard statements 1855:Fire sprinkler system 1835:Fire-retardant fabric 713: 564:In the United Kingdom 502: 494: 486: 430: 314: 306: 156: 144: 2209:Professions, trades, 2122:Smokeproof enclosure 1982:Electromagnetic lock 1690:Flammability diagram 1601:Fundamental concepts 790:public address racks 669:improve this section 548:In the United States 345:source. A dedicated 63:improve this article 2488:American inventions 2165:Fire alarm call box 2072:Heat and smoke vent 1524:on 20 February 2015 1154:"UNE 23007-14:2014" 953:Multiple-alarm fire 624:Residential systems 388:incandescent lights 343:alternating current 78:"Fire alarm system" 2137:Fire alarm systems 1952:Annulus (firestop) 1880:Flashback arrestor 1845:Fire-safe polymers 1840:Fire retardant gel 1695:Flammability limit 1082:on 29 January 2019 720: 505: 497: 489: 433: 423:Initiating devices 317: 309: 163: 151: 2470: 2469: 2378:Safety data sheet 2373:List of S-phrases 2368:List of R-phrases 2264:Sprinkler fitting 2155:Circuit integrity 2027:Fire extinguisher 1865:Firefighting foam 1760:Thermal radiation 1330:978-1-4577-1303-3 1184:shop.bsigroup.com 904: 903: 705: 704: 697: 484: 460:fire gas detector 167:fire alarm system 139: 138: 131: 113: 16:(Redirected from 2495: 2458: 2457: 2446: 2445: 2362:Life Safety Code 1967:Compartmentation 1777: 1700:Flammable liquid 1587: 1580: 1573: 1564: 1563: 1534: 1533: 1531: 1529: 1520:. Archived from 1510: 1504: 1503: 1501: 1499: 1485: 1479: 1478: 1471: 1465: 1464: 1453:. pp. 5–8. 1442: 1436: 1430: 1424: 1423: 1411: 1405: 1404: 1392: 1386: 1385: 1383: 1381: 1375: 1364: 1358: 1357: 1355: 1353: 1348:on 13 March 2020 1347: 1341:. Archived from 1306: 1295: 1289: 1288: 1276: 1270: 1269: 1267: 1265: 1251: 1245: 1244: 1242: 1240: 1226: 1220: 1219: 1217: 1215: 1201: 1195: 1194: 1192: 1190: 1176: 1170: 1169: 1167: 1165: 1150: 1144: 1143: 1141: 1139: 1124: 1118: 1117: 1115: 1113: 1098: 1092: 1091: 1089: 1087: 1078:. Archived from 1068: 1062: 1061: 1059: 1057: 1043: 1037: 1036: 1027: 1021: 1020: 1018: 1016: 1001: 830: 829: 795:background music 700: 693: 689: 686: 680: 649: 641: 485: 437:fire alarm boxes 276:United Kingdom, 134: 127: 123: 120: 114: 112: 71: 47: 39: 21: 2503: 2502: 2498: 2497: 2496: 2494: 2493: 2492: 2473: 2472: 2471: 2466: 2434: 2408: 2387: 2315: 2268: 2210: 2204: 2131: 2057:Firestop pillow 1992:Emergency light 1945:Building design 1940: 1931:Tank blanketing 1900:Inerting system 1875:Flame retardant 1825:Fire protection 1820:Fire prevention 1778: 1769: 1634:Dangerous goods 1596: 1594:Fire protection 1591: 1543: 1538: 1537: 1527: 1525: 1512: 1511: 1507: 1497: 1495: 1487: 1486: 1482: 1473: 1472: 1468: 1461: 1443: 1439: 1431: 1427: 1412: 1408: 1393: 1389: 1379: 1377: 1373: 1365: 1361: 1351: 1349: 1345: 1331: 1304: 1296: 1292: 1277: 1273: 1263: 1261: 1253: 1252: 1248: 1238: 1236: 1228: 1227: 1223: 1213: 1211: 1203: 1202: 1198: 1188: 1186: 1178: 1177: 1173: 1163: 1161: 1152: 1151: 1147: 1137: 1135: 1126: 1125: 1121: 1111: 1109: 1102:"UNI 9795:2013" 1100: 1099: 1095: 1085: 1083: 1070: 1069: 1065: 1055: 1053: 1045: 1044: 1040: 1029: 1028: 1024: 1014: 1012: 1002: 998: 993: 944: 909: 804: 781:fire sprinklers 701: 690: 684: 681: 666: 650: 639: 626: 575: 566: 550: 525: 480: 478: 472: 425: 374:smoke detectors 301: 203: 179:carbon monoxide 135: 124: 118: 115: 72: 70: 60: 48: 35: 28: 23: 22: 15: 12: 11: 5: 2501: 2491: 2490: 2485: 2468: 2467: 2465: 2464: 2452: 2439: 2436: 2435: 2433: 2432: 2427: 2422: 2416: 2414: 2410: 2409: 2407: 2406: 2401: 2395: 2393: 2389: 2388: 2386: 2385: 2380: 2375: 2370: 2365: 2359: 2354: 2349: 2344: 2339: 2334: 2329: 2323: 2321: 2317: 2316: 2314: 2313: 2307: 2301: 2295: 2289: 2283: 2276: 2274: 2270: 2269: 2267: 2266: 2261: 2256: 2251: 2246: 2240: 2235: 2230: 2225: 2223:Fire insurance 2220: 2214: 2212: 2206: 2205: 2203: 2202: 2200:Smoke detector 2197: 2192: 2187: 2185:Flame detector 2182: 2177: 2172: 2167: 2162: 2157: 2152: 2147: 2141: 2139: 2133: 2132: 2130: 2129: 2124: 2119: 2114: 2109: 2104: 2099: 2094: 2089: 2084: 2079: 2074: 2069: 2064: 2059: 2054: 2049: 2047:Fire sprinkler 2044: 2039: 2034: 2029: 2024: 2019: 2014: 2009: 2004: 1999: 1994: 1989: 1987:Emergency exit 1984: 1979: 1974: 1969: 1964: 1959: 1957:Area of refuge 1954: 1948: 1946: 1942: 1941: 1939: 1938: 1933: 1928: 1926:Spark arrestor 1923: 1918: 1912: 1907: 1902: 1897: 1892: 1887: 1882: 1877: 1872: 1870:Flame arrester 1867: 1862: 1857: 1852: 1847: 1842: 1837: 1832: 1830:Fire retardant 1827: 1822: 1817: 1812: 1807: 1802: 1797: 1792: 1786: 1784: 1780: 1779: 1772: 1770: 1768: 1767: 1765:Water pressure 1762: 1757: 1755:Structure fire 1752: 1747: 1742: 1737: 1732: 1727: 1722: 1717: 1712: 1707: 1702: 1697: 1692: 1687: 1682: 1677: 1672: 1667: 1662: 1657: 1652: 1650:Dust explosion 1647: 1642: 1637: 1631: 1626: 1621: 1616: 1610: 1604: 1602: 1598: 1597: 1590: 1589: 1582: 1575: 1567: 1561: 1560: 1558:NFPA Standards 1555: 1550: 1542: 1541:External links 1539: 1536: 1535: 1505: 1480: 1466: 1459: 1437: 1425: 1406: 1387: 1359: 1329: 1290: 1271: 1246: 1221: 1196: 1171: 1145: 1132:Afnor EDITIONS 1119: 1093: 1063: 1038: 1022: 995: 994: 992: 989: 988: 987: 981: 975: 970: 965: 963:Smoke detector 960: 955: 950: 943: 940: 936: 935: 932: 929: 926: 923: 920: 913:BS 5839 Part 1 908: 905: 902: 901: 897: 893: 892: 888: 884: 883: 879: 875: 874: 870: 866: 865: 861: 857: 856: 852: 848: 847: 843: 839: 838: 834: 825: 824: 821: 818: 808:BS 5839 Part 1 803: 800: 799: 798: 785: 784: 767: 766: 746: 745: 729:electromagnets 703: 702: 653: 651: 644: 638: 635: 630:security alarm 625: 622: 601: 600: 597: 594: 574: 571: 565: 562: 549: 546: 524: 521: 474:Main article: 471: 468: 456:flame detector 452:radiant energy 448:smoke detector 424: 421: 420: 419: 415: 377: 370:heat detectors 362: 351: 347:branch circuit 339: 327: 300: 297: 296: 295: 281: 280: 278:BS 5839 Part 1 274: 268: 262: 256: 242: 241: 229: 228: 214: 202: 199: 137: 136: 51: 49: 42: 26: 9: 6: 4: 3: 2: 2500: 2489: 2486: 2484: 2481: 2480: 2478: 2463: 2462: 2453: 2451: 2450: 2441: 2440: 2437: 2431: 2430:Template:HVAC 2428: 2426: 2423: 2421: 2420:Template:Fire 2418: 2417: 2415: 2411: 2405: 2402: 2400: 2397: 2396: 2394: 2390: 2384: 2381: 2379: 2376: 2374: 2371: 2369: 2366: 2363: 2360: 2358: 2355: 2353: 2350: 2348: 2345: 2343: 2340: 2338: 2335: 2333: 2330: 2328: 2325: 2324: 2322: 2318: 2311: 2308: 2305: 2302: 2299: 2296: 2293: 2290: 2287: 2284: 2281: 2278: 2277: 2275: 2271: 2265: 2262: 2260: 2257: 2255: 2252: 2250: 2247: 2244: 2241: 2239: 2236: 2234: 2231: 2229: 2226: 2224: 2221: 2219: 2218:Duct cleaning 2216: 2215: 2213: 2207: 2201: 2198: 2196: 2193: 2191: 2190:Heat detector 2188: 2186: 2183: 2181: 2178: 2176: 2173: 2171: 2168: 2166: 2163: 2161: 2158: 2156: 2153: 2151: 2148: 2146: 2143: 2142: 2140: 2138: 2134: 2128: 2125: 2123: 2120: 2118: 2115: 2113: 2110: 2108: 2107:Smoke control 2105: 2103: 2100: 2098: 2095: 2093: 2090: 2088: 2085: 2083: 2080: 2078: 2075: 2073: 2070: 2068: 2065: 2063: 2060: 2058: 2055: 2053: 2050: 2048: 2045: 2043: 2040: 2038: 2035: 2033: 2030: 2028: 2025: 2023: 2020: 2018: 2015: 2013: 2010: 2008: 2005: 2003: 2000: 1998: 1995: 1993: 1990: 1988: 1985: 1983: 1980: 1978: 1975: 1973: 1970: 1968: 1965: 1963: 1960: 1958: 1955: 1953: 1950: 1949: 1947: 1943: 1937: 1934: 1932: 1929: 1927: 1924: 1922: 1919: 1916: 1913: 1911: 1908: 1906: 1903: 1901: 1898: 1896: 1893: 1891: 1888: 1886: 1883: 1881: 1878: 1876: 1873: 1871: 1868: 1866: 1863: 1861: 1858: 1856: 1853: 1851: 1848: 1846: 1843: 1841: 1838: 1836: 1833: 1831: 1828: 1826: 1823: 1821: 1818: 1816: 1813: 1811: 1808: 1806: 1803: 1801: 1798: 1796: 1793: 1791: 1788: 1787: 1785: 1781: 1776: 1766: 1763: 1761: 1758: 1756: 1753: 1751: 1748: 1746: 1743: 1741: 1738: 1736: 1733: 1731: 1728: 1726: 1725:Heat transfer 1723: 1721: 1718: 1716: 1715:Friction loss 1713: 1711: 1708: 1706: 1703: 1701: 1698: 1696: 1693: 1691: 1688: 1686: 1685:Fire triangle 1683: 1681: 1678: 1676: 1673: 1671: 1668: 1666: 1663: 1661: 1658: 1656: 1653: 1651: 1648: 1646: 1643: 1641: 1638: 1635: 1632: 1630: 1629:Conflagration 1627: 1625: 1622: 1620: 1617: 1614: 1611: 1609: 1606: 1605: 1603: 1599: 1595: 1588: 1583: 1581: 1576: 1574: 1569: 1568: 1565: 1559: 1556: 1554: 1551: 1549: 1545: 1544: 1523: 1519: 1515: 1509: 1494: 1490: 1484: 1476: 1470: 1462: 1460:0-87765-377-1 1456: 1452: 1448: 1441: 1434: 1429: 1421: 1417: 1410: 1402: 1398: 1391: 1372: 1371: 1363: 1344: 1340: 1336: 1332: 1326: 1322: 1318: 1314: 1310: 1303: 1302: 1294: 1286: 1282: 1275: 1260: 1256: 1250: 1235: 1231: 1225: 1210: 1206: 1200: 1185: 1181: 1175: 1159: 1155: 1149: 1133: 1129: 1123: 1107: 1106:store.uni.com 1103: 1097: 1081: 1077: 1073: 1067: 1052: 1048: 1042: 1034: 1033: 1026: 1011: 1007: 1000: 996: 985: 982: 979: 976: 974: 971: 969: 966: 964: 961: 959: 956: 954: 951: 949: 946: 945: 939: 933: 930: 927: 924: 921: 918: 917: 916: 914: 898: 895: 894: 889: 886: 885: 880: 877: 876: 871: 868: 867: 862: 859: 858: 853: 850: 849: 844: 841: 840: 835: 832: 831: 828: 822: 819: 816: 815: 814: 811: 809: 796: 791: 787: 786: 782: 777: 773: 769: 768: 764: 760: 756: 752: 748: 747: 743: 738: 734: 730: 726: 722: 721: 717: 712: 708: 699: 696: 688: 678: 674: 670: 664: 663: 659: 654:This section 652: 648: 643: 642: 634: 631: 621: 619: 615: 611: 607: 598: 595: 592: 591: 590: 587: 585: 581: 570: 561: 559: 554: 545: 542: 537: 533: 530: 520: 518: 514: 509: 501: 493: 477: 467: 465: 461: 457: 453: 449: 445: 444:heat detector 440: 438: 429: 416: 413: 409: 405: 401: 397: 393: 392:strobe lights 389: 385: 381: 378: 375: 371: 367: 363: 360: 356: 352: 348: 344: 340: 337: 333: 328: 325: 322: 321: 320: 313: 305: 293: 290: 289: 288: 286: 279: 275: 273: 269: 267: 263: 261: 257: 255: 251: 250: 249: 247: 239: 234: 231: 230: 226: 222: 218: 215: 212: 209: 208: 207: 198: 196: 192: 191:signalization 188: 184: 183:pull stations 180: 176: 172: 168: 160: 155: 148: 143: 133: 130: 122: 111: 108: 104: 101: 97: 94: 90: 87: 83: 80: –  79: 75: 74:Find sources: 68: 64: 58: 57: 52:This article 50: 46: 41: 40: 37: 33: 19: 2460: 2448: 2347:Flame spread 2233:Fireproofing 2211:and services 2136: 2112:Smoke damper 2102:Safety glass 2037:Fire hydrant 2002:Fire curtain 1962:Booster pump 1921:Relief valve 1885:Fusible link 1675:Fire loading 1670:Fire control 1640:Deflagration 1526:. Retrieved 1522:the original 1508: 1496:. Retrieved 1492: 1483: 1469: 1446: 1440: 1432: 1428: 1415: 1409: 1396: 1390: 1378:. Retrieved 1369: 1362: 1350:. Retrieved 1343:the original 1300: 1293: 1284: 1274: 1262:. Retrieved 1258: 1249: 1237:. Retrieved 1233: 1224: 1212:. Retrieved 1208: 1199: 1187:. Retrieved 1183: 1174: 1162:. Retrieved 1160:(in Spanish) 1157: 1148: 1136:. Retrieved 1131: 1128:"NF S61-936" 1122: 1110:. Retrieved 1108:(in Italian) 1105: 1096: 1084:. Retrieved 1080:the original 1075: 1066: 1054:. Retrieved 1050: 1041: 1031: 1025: 1013:. Retrieved 1010:Coopers Fire 1009: 999: 937: 910: 826: 812: 805: 776:fire service 737:demagnetizes 706: 691: 685:January 2011 682: 667:Please help 655: 627: 610:text message 602: 588: 576: 567: 555: 551: 538: 534: 528: 526: 510: 506: 441: 434: 412:loudspeakers 318: 282: 272:UNE 23007-14 243: 220: 204: 166: 164: 125: 116: 106: 99: 92: 85: 73: 61:Please help 56:verification 53: 36: 2067:Grease duct 2022:Fire escape 2012:Fire damper 1905:Intumescent 1850:Fire safety 1815:Fire bucket 1710:Flash point 1528:20 February 1158:www.une.org 1134:(in French) 973:False alarm 759:conditioned 742:radio waves 390:, flashing 211:ISO 7240-14 147:annunciator 18:Fire alarms 2477:Categories 2364:(NFPA 101) 2327:CE marking 2180:Fire drill 1783:Technology 1680:Fire point 1665:Fire class 1645:Detonation 991:References 968:Fire drill 753:and other 359:generators 350:appliance. 266:NF S61-936 119:March 2024 89:newspapers 2320:Standards 2249:Fire test 2077:Occupancy 2042:Fire pump 2032:Fire hose 2017:Fire door 1997:Exit sign 1972:Crash bar 1745:Pyrolysis 1740:Pool fire 1705:Flashover 1660:Explosive 1608:Backdraft 1321:1826/7588 725:solenoids 656:does not 517:emergency 513:odorizers 292:Australia 252:Germany, 246:TS 54 -14 233:TS 54 -14 195:elevators 2449:Category 2413:See also 2342:EN 16034 2052:Firestop 2007:Fire cut 1730:Jet fire 1720:Gas leak 1636:(HAZMAT) 1619:Boilover 1498:21 March 1380:9 August 1339:11394788 1264:27 April 1239:27 April 1214:27 April 1189:26 March 1164:26 March 1138:26 March 1112:26 March 1086:26 March 1056:26 March 942:See also 772:elevator 751:ductwork 614:RSS feed 541:highrise 384:evacuate 332:commands 264:France, 260:UNI 9795 254:Vds 2095 2461:Commons 2294:(NCEES) 1615:(BLEVE) 1493:Geofire 1352:8 April 1015:12 July 763:dampers 755:plenums 677:removed 662:sources 558:NFPA 72 556:As per 464:cameras 285:Oceania 283:Across 270:Spain, 258:Italy, 103:scholar 2392:Awards 2306:(SFPE) 2300:(NFPA) 2282:(FEMA) 2245:(FSES) 1457:  1376:. IEEE 1337:  1327:  907:Zoning 788:Audio 714:Coded 454:for a 418:exits. 404:chimes 400:sirens 366:inputs 201:Design 105:  98:  91:  84:  76:  2383:UL 94 2337:EN 54 2288:(IFE) 1917:(PPE) 1374:(PDF) 1346:(PDF) 1335:S2CID 1305:(PDF) 978:EN 54 733:doors 616:, or 606:email 408:bells 396:horns 299:Parts 238:EN 54 175:smoke 110:JSTOR 96:books 2332:EN 3 2312:(UL) 1530:2015 1500:2018 1455:ISBN 1382:2018 1354:2013 1325:ISBN 1266:2023 1241:2023 1216:2023 1191:2022 1166:2022 1140:2022 1114:2022 1088:2022 1058:2022 1017:2023 660:any 658:cite 219:72, 217:NFPA 171:fire 82:news 1317:hdl 1309:doi 1076:VdS 896:L5 887:L4 878:L3 869:L2 860:L1 851:P2 842:P1 727:or 671:by 618:IVR 539:In 336:LCD 65:by 2479:: 1516:. 1491:. 1449:. 1418:. 1399:. 1333:. 1323:. 1315:. 1283:. 1257:. 1232:. 1207:. 1182:. 1156:. 1130:. 1104:. 1074:. 1049:. 1008:. 915:: 833:M 783:). 612:, 608:, 586:. 450:, 410:, 406:, 402:, 398:, 394:, 248:: 177:, 173:, 165:A 157:A 1586:e 1579:t 1572:v 1532:. 1502:. 1477:. 1463:. 1384:. 1356:. 1319:: 1311:: 1287:. 1268:. 1243:. 1218:. 1193:. 1168:. 1142:. 1116:. 1090:. 1060:. 1035:. 1019:. 698:) 692:( 687:) 683:( 679:. 665:. 376:. 132:) 126:( 121:) 117:( 107:· 100:· 93:· 86:· 59:. 34:. 20:)

Index

Fire alarms
Fire alarm (disambiguation)

verification
improve this article
adding citations to reliable sources
"Fire alarm system"
news
newspapers
books
scholar
JSTOR
Learn how and when to remove this message

annunciator

fire alarm notification appliance
fire
smoke
carbon monoxide
pull stations
fire alarm control panel
signalization
elevators
ISO 7240-14
NFPA
Underwriters' Laboratories of Canada
TS 54 -14
EN 54
TS 54 -14

Text is available under the Creative Commons Attribution-ShareAlike License. Additional terms may apply.