Knowledge

Distribution board

Source đź“ť

680: 700: 1183:, but sometimes they are also featured as part of the aesthetic elements of a building (as an art installation, for example) or where they can be easily accessible. However, current U.S. building codes prohibit installation of a panel in a bathroom (or similar room), in closets intended for clothing, or where there is insufficient space for an electrician to gain access to the panel. Specific situations, such as an installation outdoors, in a hazardous environment, or in other out-of-the-ordinary locations might require specialized equipment and more stringent installation practices. 1029: 712: 664: 724: 901: 877: 835: 913: 889: 1608: 2187: 827: 749: 1145: 761:, for neutral and earth. The incoming neutral connects to the lower busbar on the right side of the panel, which is in turn connected to the neutral busbar at the top left. The incoming earth wire connects to the lower busbar on the left side of the panel, which is in turn connected to the earth busbar at the top right. The cover has been removed from the lower-right neutral bar; the neutral bar on the left side has its cover in place. 32: 863:(MCBs). A normal new domestic CU used as a main panel might have from 6 to 24 ways for devices (some of which might occupy two ways), and will be split into two or more sections (e.g. a non-RCD section for alarms etc., an RCD-protected section for socket outlets, and an RCD-protected section for lighting and other built-in appliances). Secondary CUs used for outbuildings usually have 1 to 4 ways plus an RCD. 933:
protective device will depend upon the type of electrical circuit it is protecting and what level of protection needs to be afforded. BS7671:2018 Requirements for Electrical Installations, also referred to as the IET Wiring Regulations, gets regularly updated and its latest edition at the time of writing is amendment 2:2022 released on 28 March 2022. Typical configurations of CU:
679: 654:
configuration appears to display two violations of the current U.S. National Electric Code: the main panel does not have a grounding conductor (here it is fed through the subpanel instead) and the subpanel neutral bar is bonded to the ground bar (these should be separate bars after the first service disconnect, which in this case is the main panel).
962:
sensitive devices such as RCBOs and AFDDs would not be appropriate, or the independent use of RCBOs, and may be limited to only one or two ways. The remainder of the circuits are divided in the same way as a dual RCD CU. This type of consumer unit offers improved circuit separation over a dual RCD CU whilst allowing for more flexibility.
1136:
assemblies have been tested and approved for use by a recognized authority. Replacing or adding equipment which "just happens to fit" can result in unexpected or even dangerous conditions. Such installations should not be done without first consulting knowledgeable sources, including manufacturers' datasheets.
1081:
Another way to protect circuits under the 17th Edition IET Wiring Regulations is by fitting Residual Current Circuit Breaker With Overload (RCBOs) to every circuit, and although this is more costly than the RCD+MCB's option, it means any fault condition on a circuit trips only that circuit's RCBO, so
1077:
By arranging the circuits like this, power will still be present on one of the floors if only one RCD trips out. Moreover, having sockets and lights on alternate RCD's means that if a faulty kettle downstairs trips that RCD for example, the kitchen lights will still be available, avoiding the hazard
965:
RCD incomer consumer unit - This is the least convenient solution in terms of circuit separation because the main switch is an RCD. Less common than the other types, it is no longer considered a standalone solution because power to all circuits is lost in the event of an earth fault causing the main
923:
Fuse boxes normally use cartridge or rewirable fuses with no other protective device, and basic 4-ways boxes are very common. Some older boxes are made of brown-black bakelite, sometimes with a wooden base. Although their design is historic, these were standard equipment for new installs as recently
937:
Main switch consumer unit - Consists of a main switch that will disconnect power to all circuits simultaneously which has one busbar linking all protective devices to a common live source, and one neutral conductor or link bar connecting to a common neutral rail. There will be a separate earth rail
638:
to the left with all the white wires, and the two hot wires are attached to the main breaker. Below the main breaker are the two bus bars carrying the current between the main breaker and the two columns of branch circuit breakers, with each respective circuit's red and black hot wires leading off.
1219:
Distribution boards may be surface-mounted or flush. The former arrangement provides easier alteration or addition to wiring at a later date, but the latter arrangement might be neater, particularly for a residential application. The other problem with recessing a distribution board into a wall is
850:
as "A particular type of distribution board comprising a type tested coordinated assembly for the control and distribution of electrical energy, principally in domestic premises..." These installations usually have single-phase supplies at 230 V (nominal standard); historically, they were known as
739:
A common design of fuse box that was featured in homes built from 1940 through 1965 was the 60-amp fuse box that included four plug fuses (i.e. the Edison base) for branch circuits and one or more fuse blocks containing cartridge fuses for purposes such as major appliance circuits. After 1965, the
1135:
for mounting and a standard cut-out shape for seemingly interchangeable breakers, the positions of busbar connections and other features are not standardized. Each manufacturer has one or more "systems", or kinds of breaker panels, that is only fully compatible with breakers of that type. These
1207:
arrangement. The dimmers are equally divided across the three incoming phases. In a 96 dimmer rack, there are 32 dimmers on phase A, 32 dimmers on phase B, and 32 on phase C to spread out the lighting load as equally as possible. In addition to the power feed from the supply transformer in the
961:
High integrity consumer unit - Consists of a main switch that will disconnect power to all circuits simultaneously and three separate live busbars, one linked directly to the main switch and two others on each main RCD. The live busbar on the main switch allows the use of mcbs only where more
653:
The photograph on the left shows a dual panel configuration: a main panel on the right (with front cover in place) and a subpanel on the left (with cover removed). The subpanel is fed by two large hot wires and a neutral wire running through the angled conduit near the top of the panels. This
1186:
Distribution boards may be designated for three phase or single phase and normal power or emergency power, or designated by use such as distribution panels for supplying other panels, lighting panels for lights, power panels for equipment and receptacles and special uses. Panels are located
932:
In the UK, consumer units (CU) have evolved from basic main switch and rewireable fuses, that afforded only overload and short circuit protection, into sophisticated control units housing many safety features that can protect against different types of electrical fault. The choice of circuit
768:
and two single-pole breakers, one unused. The two-pole RCBOs in the picture are not connected across two phases, but have supply-side neutral connections exiting behind the phase busbars. Down the right side of the busbars are a single-pole breaker, a two-pole RCBO and a three-pole breaker.
1082:
the search for the fault is narrowed down from the start. When an electrician must be called out, this localised fault can be resolved faster (and therefore cheaper) in contrast with the RCD+MCB's arrangement, which only indicates a fault somewhere within that RCD's set of circuits.
1036:
Since the introduction of (BS 7671:2008 incorporating amendment no 1: 2011) 17th Edition IET Wiring Regulations, consumer units in the UK must provide RCD protection to all cables embedded in walls excepting high integrity circuits such as those for burglar alarms or smoke alarms.
981:
The choice of consumer unit will reflect several factors such as the size and layout of the dwelling, number of floors, outbuildings, the expected loads (lighting, sockets, ovens, showers, immersion heaters, car-chargers etc.), and how much protection is required for each circuit.
957:
each with its own live busbar each protecting a separate bank of circuits, typically half-and-half but other combinations are available, from earth leakage faults. Offers a cost-effective solution by using a combination of cheaper mcbs and only two, more expensive,
938:
to allow the main earth conductor to be connected. This example offers the highest degree of circuit separation as all circuits are independent. This particular example amay not be suitable as a standalone solution with only overload and short circuit protection
495:
below), to allow 2- or 3-pole common-trip breakers to have one pole on each phase. In North America, it is common to wire large permanently installed equipment line-to-line. This takes two slots in the panel (two-pole) and gives a voltage of 240 V for
466:
During servicing of the distribution board, when the cover has been removed and the cables are visible, American panelboards commonly have some live parts exposed. In Canadian service entrance panelboards the main switch or circuit breaker is located in a
1202:
is used to feed stage lighting instruments. A U.S. style dimmer rack has a 208Y/120 volt 3-phase feed. Instead of just circuit breakers, the rack has a solid state electronic dimmer with its own circuit breaker for each stage circuit. This is known as a
800:. In split-phase panels, separate busbars are fed directly from the incomer, which allows RCDs to be used to protect groups of circuits. Alternatively RCBOs may be used to provide both overcurrent and residual-current protection to single circuits. 866:
Recent (pre-17th edition wiring regulations) CUs would not normally have RCD protected sections for anything other than socket outlets, though some older CUs featured RCD incomers. Before 1990, RCDs (and split busbars) were not standard in CUs.
479:
Breakers are usually arranged in two columns. In a U.S.-style board, breaker positions are numbered left-to-right, along each row from top to bottom. This numbering system is universal with numerous competitive manufacturers of breaker panels.
740:
more substantial 100 A panel with three-wire (230 V) service became common; a fuse box could have fuse blocks for the main shut-off and an electric range circuit plus a number of plug fuses (Edison base or Type S) for individual circuits.
775:
Larger commercial, public, and industrial installations generally use three-phase supplies, with distribution boards which have twin vertical rows of breakers. Larger installations will often use subsidiary distribution boards.
756:
This picture shows the interior of a typical distribution panel in the United Kingdom. The three incoming phase wires connect to the busbars via a main switch in the centre of the panel. On each side of the panel are two
1220:
that if the wall is solid, a lot of brick or block might need to be removed—generally for this reason, recessed boards would only be installed on new-build projects when the required space can be built into the wall.
1110:
A small number of pre-1950 fuseboxes are still in service. These should be treated with caution because exposed live parts are common on these boxes. The installations they supply will not meet modern standards for
1216:. The information includes lighting level information for each channel, by which it controls which dimmer circuits come up and go out during the lighting changes of the show (light cues), and over what fade time. 1009:). There were a number of similar designs from other manufacturers but the Wylex ones are by far the most commonly encountered and the only ones for which fuseholders/breakers are still commonly available. 471:, a section of the enclosure separated from the rest of the panelboard, so that when the main switch or breaker is switched off no live parts are exposed when servicing the branch circuits. 1123:. In rare instances, old ring circuits may be encountered with no fewer than 4 15 A fuses per ring, one on each of L and N, and this duplicated for each of the two feeds for the ring. 699: 772:
The illustrated panel includes a great deal of unused space; it is likely that the manufacturer produces 18- and 24-position versions of this panel using the same chassis.
427:; that is to say the front of the enclosure (whether it has a door or not) prevents the operator of the circuit breakers from contacting live electrical parts within. 423:
positioned in two columns operable from the front. Some panelboards are provided with a door covering the breaker switch handles, but all are constructed with a
1040:
Consumer units have different methods of protecting circuits. For example, a dual split-load consumer unit can be arranged in a two-story dwelling as follows:
447:
are more common in commercial and industrial applications and employ bolt-on breakers. Residential and light commercial panels are generally referred to as
331: 663: 1416: 779:
In both cases, modern boards handling supplies up to around 100 A (CUs) or 200 A (distribution boards) use circuit breakers and RCDs on
1459: 985:
The box pictured top-right is a "Wylex standard" fitted with rewirable fuses. These boxes can also be fitted with cartridge fuses or miniature
953:
Main Switch and Dual RCD consumer unit - Consists of a main switch that will disconnect power to all circuits simultaneously and two 30mA RCDs
634:. The three service conductors—two 'hot' lines and one neutral—can be seen coming in at the top. The neutral wire is connected to the neutral 723: 685:
Illustration of breaker numbering in a North American type panelboard. Some labels are missing, and some are additional. The numbers on the
2132: 924:
as the 1980s, so they are very common. Fuseholders in these boxes may not provide protection from accidental contact with live terminals.
1364: 1330: 978:
arrangements are not. Mixing of different brands devices is against the manufacturers requirements and should generally be avoided.
639:
Three wires (hot black, neutral white, and bare ground) can be seen exiting the left side of the enclosure running directly to a
324: 150: 96: 68: 1293: 2216: 2190: 1607: 75: 2029: 787:) which switches the phase and neutral lines for the whole supply. (n.b., an incomer may be referred to, or sold as, an 214: 49: 2137: 1452: 1324: 317: 145: 1757: 1006: 115: 1085:
Some older systems such as those that use MK or old MEM Consumer Units that had one fuse per spur, so for instance:
900: 876: 82: 711: 1920: 1845: 1716: 783:
mountings. The main distribution board in an installation will also normally provide a main switch (known as an
1115:. Another characteristic of very old installations is that there may be two fuses for each circuit; one on the 912: 888: 64: 53: 2092: 2024: 2014: 1890: 1790: 1445: 650:
plugged into it. The incoming bare, stranded ground wire can be seen near the bottom of the neutral bus bar.
260: 255: 1273: 1020:
strip light to their 'Lumo' consumer unit to enhance visibility in dark locations such as under staircases.
1945: 1905: 1482: 239: 459:
conductors are secured to a terminal block attached directly to the panelboard enclosure, which is itself
2172: 2167: 1885: 1860: 1850: 1826: 1821: 1527: 1167:
and security, domestic circuit breaker panels and consumer units are normally located in out-of-the-way
2211: 2087: 1805: 1775: 1552: 501: 497: 199: 943: 2142: 1631: 1592: 20: 2117: 1925: 1865: 1522: 1249: 1229: 793:, but this is problematic, as it will not necessarily be used as an isolator in the strict sense.) 630:
The photograph to the right shows the interior of a residential service panelboard manufactured by
265: 183: 178: 2056: 2046: 2036: 994: 954: 765: 393: 285: 42: 1394: 852: 397: 89: 1977: 1840: 1623: 1512: 1352: 997:(RCD) protection for sockets that could "reasonably be expected to" supply outdoor equipment ( 403:
In the United Kingdom, a distribution board designed for domestic installations is known as a
2112: 1880: 1875: 1855: 1384:
IET Wiring Regulations Seventeenth Edition - British Standard BS7671:2008, Part 2 Definitions
1310: 643: 373: 1706: 1468: 1239: 460: 385: 1028: 830:
Old Wylex standard consumer unit fitted with seven wire fuses (one fuse-way is not in use)
8: 2077: 1910: 1810: 1785: 1738: 1547: 1537: 1502: 1360: 1112: 1951: 1562: 1316: 1120: 456: 451:
and employ plug-in breakers. The neutral conductors are secured to a neutral bus using
369: 219: 209: 640: 2102: 1982: 1587: 1320: 1289: 1244: 1156: 1116: 1002: 970:
Modern consumer units are now required to be metal (non-combustible) and usually use
856: 377: 280: 131: 2051: 1992: 1696: 1691: 1668: 1577: 1517: 631: 305: 2082: 2041: 2019: 1900: 1870: 1835: 1795: 1597: 986: 939: 860: 789: 420: 381: 270: 159: 2107: 2097: 1895: 1507: 1187:
throughout the building in electric closets serving a section of the building.
1176: 990: 693:
before tripping. The top right breaker (Rated at 100 A) feeds a sub panel.
452: 229: 224: 1395:"Google search on UK availability of Modern breakers for older consumer units" 2205: 2127: 1915: 1800: 1780: 1711: 1701: 1658: 1542: 1497: 1234: 1209: 686: 295: 2147: 2122: 1987: 1956: 1770: 1572: 1152:
enters through the side of this main service panel consisting of three 100
1149: 275: 234: 834: 814:
New British distribution boards generally have the live parts enclosed to
1972: 1940: 1733: 1721: 1641: 1567: 1557: 1487: 838:
Hager consumer unit fitted with MCBs, one RCD, and one double-pole switch
804: 435:) conductors to the breakers, which are secured to the bus with either a 416: 1935: 1930: 1743: 1726: 1582: 1437: 1254: 1164: 808: 647: 204: 826: 748: 1651: 1646: 1532: 1492: 1144: 1013: 173: 31: 1765: 1308: 1180: 1132: 971: 780: 811:(relays; e.g. for large motor or heating loads) may also be used. 1686: 1676: 1417:"Innovative Bury company recognised with three award nominations" 1213: 1212:
carries information to the dimmers in a control protocol such as
998: 843: 815: 729:
An older style fuse box of the variety used in the United States.
168: 1681: 1197: 1168: 1153: 975: 797: 758: 705:
Electrical panel and subpanel with cover removed from subpanel.
690: 635: 428: 389: 300: 1172: 950:
may be required by BS7671 making this an expensive solution.
1636: 947: 942:
for each circuit. Additional protection from earth leakage
415:
North American distribution boards are generally housed in
1012:
Some manufacturers have added innovative features such as
1017: 764:
Down the left side of the phase busbars are two two-pole
1286:
C22.2 No. 29-15 — "Panelboards and enclosed panelboards"
989:(MCBs). This type of consumer unit was very popular in 16:
Component of an electricity supply system housing fuses
974:
mounted devices. The DIN rail is standardized but the
818:, even when the cover has been removed for servicing. 372:
that divides an electrical power feed into subsidiary
398:
residual current breakers with overcurrent protection
1288:. Canadian Standards Association. 2015. p. 40. 56:. Unsourced material may be challenged and removed. 2203: 1312:Black & Decker The Complete Guide to Wiring 19:"Fuse box" redirects here. For other uses, see 1032:Modern RCD Protection Consumer Dual Split-Load 1453: 325: 1309:The editors of Creative Publishing (2008). 993:until 2001 when wiring regulations mandated 669:An American circuit breaker panel featuring 1195:In a theatre, a specialty panel known as a 1139: 1126: 1460: 1446: 332: 318: 439:connection (using a threaded screw) or a 116:Learn how and when to remove this message 1467: 1143: 1078:of investigating the fault in darkness. 1027: 833: 825: 747: 1023: 483:Each row is fed from a different line ( 2204: 1350: 906:1970s MEM rewirable fuse box (covered) 882:1950s MEM rewirable fuse box (covered) 474: 431:carry the current from incoming line ( 160:Regulation of electrical installations 1441: 796:For each phase, power is fed along a 392:, and in recent boards, one or more 174:IEC 60364 IEC international standard 138:Wiring practice by region or country 54:adding citations to reliable sources 25: 1208:building, a control cable from the 1190: 1131:Despite the adoption of a standard 1105: 918:1970s MEM rewirable fuse box (open) 894:1950s MEM rewirable fuse box (open) 443:connection using a retaining clip. 215:Mineral-insulated copper-clad cable 184:U.S. National Electrical Code (NEC) 13: 2138:Renewable energy commercialization 752:One type of UK distribution board. 179:Canadian Electrical Code (CE Code) 14: 2228: 821: 743: 508:North American breaker numbering 2186: 2185: 1606: 1351:George, Daniels (January 1966). 911: 899: 887: 875: 722: 710: 698: 678: 662: 410: 248:Switching and protection devices 30: 1367:from the original on 2023-07-18 1333:from the original on 2023-07-18 855:, as older consumer units used 400:(RCBOs) are also incorporated. 41:needs additional citations for 1409: 1387: 1378: 1344: 1302: 1278: 1267: 1: 2133:Renewable Energy Certificates 2093:Cost of electricity by source 2015:Arc-fault circuit interrupter 1891:High-voltage shore connection 1260: 807:(e.g. for bell circuits) and 734: 384:for each circuit in a common 376:while providing a protective 169:BS 7671 UK wiring regulations 2148:Spark/Dark/Quark/Bark spread 1946:Transmission system operator 1906:Mains electricity by country 1483:Automatic generation control 1353:"Improving Your Home Wiring" 717:The internal wiring visible. 240:Thermoplastic-sheathed cable 7: 2217:Electric power distribution 2173:List of electricity sectors 2168:Electric energy consumption 1886:High-voltage direct current 1861:Electric power transmission 1851:Electric power distribution 1528:Energy return on investment 1223: 927: 625: 10: 2233: 2088:Carbon offsets and credits 1806:Three-phase electric power 498:split-phase electric power 200:AC power plugs and sockets 18: 2181: 2156: 2143:Renewable Energy Payments 2066: 2003: 1965: 1819: 1756: 1667: 1632:Fossil fuel power station 1622: 1615: 1604: 1475: 1098:Downstairs Sockets Fuse 4 518: 370:electricity supply system 225:Steel wire armoured cable 21:Fuse box (disambiguation) 1926:Single-wire earth return 1866:Electrical busbar system 1523:Energy demand management 1250:Electrical busbar system 1230:Circuit total limitation 1140:Location and designation 1127:Manufacturer differences 1095:Downstairs Lights Fuse 3 871:Old rewirable-fuse boxes 394:residual-current devices 266:Electrical busbar system 132:Electrical installations 2057:Residual-current device 2047:Power system protection 2037:Generator interlock kit 1092:Upstairs Sockets Fuse 2 995:residual-current device 966:switch RCD to activate. 842:In the United Kingdom, 803:Other devices, such as 368:) is a component of an 286:Residual-current device 192:Cabling and accessories 151:United Kingdom practice 146:North American practice 1841:Distributed generation 1513:Electric power quality 1160: 1089:Upstairs Lights Fuse 1 1050:Downstairs Ring Final, 1033: 946:faults and arc faults 839: 831: 753: 2113:Fossil fuel phase-out 1881:Electricity retailing 1876:Electrical substation 1856:Electric power system 1147: 1031: 861:mini-circuit breakers 837: 829: 751: 644:electrical receptacle 455:. The branch circuit 419:enclosures, with the 1469:Electricity delivery 1240:Electric switchboard 1024:RCD protection types 859:until the advent of 658:North American boxes 500:, or 208 V for 65:"Distribution board" 50:improve this article 2078:Availability factor 2030:Sulfur hexafluoride 1911:Overhead power line 1811:Virtual power plant 1786:Induction generator 1739:Sustainable biofuel 1548:Home energy storage 1538:Grid energy storage 1503:Droop speed control 1421:www.burytimes.co.uk 1361:Bonnier Corporation 689:indicate the rated 509: 475:Breaker arrangement 388:. Normally, a main 1952:Transmission tower 1563:Nameplate capacity 1317:Cool Springs Press 1205:dimmer-per-circuit 1161: 1064:Downstairs Lights, 1034: 840: 832: 754: 507: 346:distribution board 291:Distribution board 220:Multiway switching 210:Electrical conduit 2212:Electrical wiring 2199: 2198: 2103:Environmental tax 1983:Cascading failure 1752: 1751: 1588:Utility frequency 1295:978-1-77139-712-4 1245:Electricity meter 1113:electrical safety 1067:Upstairs Sockets, 1016:who have added a 621: 620: 502:three-phase power 342: 341: 301:Electrical switch 126: 125: 118: 100: 2224: 2189: 2188: 2098:Energy subsidies 2052:Protective relay 1993:Rolling blackout 1620: 1619: 1610: 1578:Power-flow study 1518:Electrical fault 1462: 1455: 1448: 1439: 1438: 1432: 1431: 1429: 1427: 1413: 1407: 1406: 1404: 1402: 1391: 1385: 1382: 1376: 1375: 1373: 1372: 1348: 1342: 1341: 1339: 1338: 1315:(4th ed.). 1306: 1300: 1299: 1282: 1276: 1271: 1191:Theatre lighting 1106:Legacy fuseboxes 1047:Upstairs Lights, 987:circuit breakers 915: 903: 891: 879: 726: 714: 702: 682: 673:circuit breakers 666: 632:General Electric 510: 506: 421:circuit breakers 334: 327: 320: 306:Earthing systems 271:Circuit breakers 128: 127: 121: 114: 110: 107: 101: 99: 58: 34: 26: 2232: 2231: 2227: 2226: 2225: 2223: 2222: 2221: 2202: 2201: 2200: 2195: 2177: 2161: 2159: 2152: 2083:Capacity factor 2071: 2069: 2062: 2042:Numerical relay 2020:Circuit breaker 2008: 2006: 1999: 1961: 1901:Load management 1871:Electrical grid 1836:Demand response 1829: 1824: 1815: 1796:Microgeneration 1748: 1663: 1611: 1602: 1598:Vehicle-to-grid 1471: 1466: 1436: 1435: 1425: 1423: 1415: 1414: 1410: 1400: 1398: 1393: 1392: 1388: 1383: 1379: 1370: 1368: 1357:Popular Science 1349: 1345: 1336: 1334: 1327: 1307: 1303: 1296: 1284: 1283: 1279: 1272: 1268: 1263: 1226: 1193: 1163:For reasons of 1142: 1129: 1119:and one on the 1108: 1053:Garage Sockets, 1026: 930: 919: 916: 907: 904: 895: 892: 883: 880: 824: 746: 737: 730: 727: 718: 715: 706: 703: 694: 683: 674: 671:interchangeable 667: 628: 477: 453:screw terminals 413: 382:circuit breaker 348:(also known as 338: 122: 111: 105: 102: 59: 57: 47: 35: 24: 17: 12: 11: 5: 2230: 2220: 2219: 2214: 2197: 2196: 2194: 2193: 2182: 2179: 2178: 2176: 2175: 2170: 2164: 2162: 2158:Statistics and 2157: 2154: 2153: 2151: 2150: 2145: 2140: 2135: 2130: 2125: 2120: 2115: 2110: 2108:Feed-in tariff 2105: 2100: 2095: 2090: 2085: 2080: 2074: 2072: 2067: 2064: 2063: 2061: 2060: 2054: 2049: 2044: 2039: 2034: 2033: 2032: 2027: 2017: 2011: 2009: 2004: 2001: 2000: 1998: 1997: 1996: 1995: 1985: 1980: 1975: 1969: 1967: 1963: 1962: 1960: 1959: 1954: 1949: 1943: 1938: 1933: 1928: 1923: 1918: 1913: 1908: 1903: 1898: 1896:Interconnector 1893: 1888: 1883: 1878: 1873: 1868: 1863: 1858: 1853: 1848: 1846:Dynamic demand 1843: 1838: 1832: 1830: 1820: 1817: 1816: 1814: 1813: 1808: 1803: 1798: 1793: 1788: 1783: 1778: 1776:Combined cycle 1773: 1768: 1762: 1760: 1754: 1753: 1750: 1749: 1747: 1746: 1741: 1736: 1731: 1730: 1729: 1724: 1719: 1714: 1709: 1699: 1694: 1689: 1684: 1679: 1673: 1671: 1665: 1664: 1662: 1661: 1656: 1655: 1654: 1649: 1644: 1639: 1628: 1626: 1617: 1613: 1612: 1605: 1603: 1601: 1600: 1595: 1590: 1585: 1580: 1575: 1570: 1565: 1560: 1555: 1553:Load-following 1550: 1545: 1540: 1535: 1530: 1525: 1520: 1515: 1510: 1508:Electric power 1505: 1500: 1495: 1490: 1485: 1479: 1477: 1473: 1472: 1465: 1464: 1457: 1450: 1442: 1434: 1433: 1408: 1386: 1377: 1343: 1326:978-1589234130 1325: 1319:. p. 75. 1301: 1294: 1277: 1274:Consumer Units 1265: 1264: 1262: 1259: 1258: 1257: 1252: 1247: 1242: 1237: 1232: 1225: 1222: 1192: 1189: 1148:A three-phase 1141: 1138: 1128: 1125: 1107: 1104: 1100: 1099: 1096: 1093: 1090: 1075: 1074: 1071: 1068: 1065: 1058: 1057: 1054: 1051: 1048: 1025: 1022: 968: 967: 963: 959: 951: 929: 926: 921: 920: 917: 910: 908: 905: 898: 896: 893: 886: 884: 881: 874: 872: 823: 822:Consumer units 820: 745: 744:United Kingdom 742: 736: 733: 732: 731: 728: 721: 719: 716: 709: 707: 704: 697: 695: 684: 677: 675: 668: 661: 659: 627: 624: 619: 618: 615: 612: 609: 605: 604: 601: 598: 595: 591: 590: 587: 584: 581: 577: 576: 573: 570: 567: 563: 562: 559: 556: 553: 549: 548: 545: 542: 539: 535: 534: 531: 528: 525: 521: 520: 517: 514: 476: 473: 412: 409: 358:electric panel 340: 339: 337: 336: 329: 322: 314: 311: 310: 309: 308: 303: 298: 293: 288: 283: 278: 273: 268: 263: 258: 250: 249: 245: 244: 243: 242: 237: 232: 230:Ring main unit 227: 222: 217: 212: 207: 202: 194: 193: 189: 188: 187: 186: 181: 176: 171: 163: 162: 156: 155: 154: 153: 148: 140: 139: 135: 134: 124: 123: 38: 36: 29: 15: 9: 6: 4: 3: 2: 2229: 2218: 2215: 2213: 2210: 2209: 2207: 2192: 2184: 2183: 2180: 2174: 2171: 2169: 2166: 2165: 2163: 2155: 2149: 2146: 2144: 2141: 2139: 2136: 2134: 2131: 2129: 2128:Pigouvian tax 2126: 2124: 2121: 2119: 2116: 2114: 2111: 2109: 2106: 2104: 2101: 2099: 2096: 2094: 2091: 2089: 2086: 2084: 2081: 2079: 2076: 2075: 2073: 2065: 2058: 2055: 2053: 2050: 2048: 2045: 2043: 2040: 2038: 2035: 2031: 2028: 2026: 2025:Earth-leakage 2023: 2022: 2021: 2018: 2016: 2013: 2012: 2010: 2002: 1994: 1991: 1990: 1989: 1986: 1984: 1981: 1979: 1976: 1974: 1971: 1970: 1968: 1966:Failure modes 1964: 1958: 1955: 1953: 1950: 1947: 1944: 1942: 1939: 1937: 1934: 1932: 1929: 1927: 1924: 1922: 1919: 1917: 1916:Power station 1914: 1912: 1909: 1907: 1904: 1902: 1899: 1897: 1894: 1892: 1889: 1887: 1884: 1882: 1879: 1877: 1874: 1872: 1869: 1867: 1864: 1862: 1859: 1857: 1854: 1852: 1849: 1847: 1844: 1842: 1839: 1837: 1834: 1833: 1831: 1828: 1823: 1818: 1812: 1809: 1807: 1804: 1802: 1801:Rankine cycle 1799: 1797: 1794: 1792: 1789: 1787: 1784: 1782: 1781:Cooling tower 1779: 1777: 1774: 1772: 1769: 1767: 1764: 1763: 1761: 1759: 1755: 1745: 1742: 1740: 1737: 1735: 1732: 1728: 1725: 1723: 1720: 1718: 1715: 1713: 1710: 1708: 1705: 1704: 1703: 1700: 1698: 1695: 1693: 1690: 1688: 1685: 1683: 1680: 1678: 1675: 1674: 1672: 1670: 1666: 1660: 1657: 1653: 1650: 1648: 1645: 1643: 1640: 1638: 1635: 1634: 1633: 1630: 1629: 1627: 1625: 1624:Non-renewable 1621: 1618: 1614: 1609: 1599: 1596: 1594: 1591: 1589: 1586: 1584: 1581: 1579: 1576: 1574: 1571: 1569: 1566: 1564: 1561: 1559: 1556: 1554: 1551: 1549: 1546: 1544: 1543:Grid strength 1541: 1539: 1536: 1534: 1531: 1529: 1526: 1524: 1521: 1519: 1516: 1514: 1511: 1509: 1506: 1504: 1501: 1499: 1498:Demand factor 1496: 1494: 1491: 1489: 1486: 1484: 1481: 1480: 1478: 1474: 1470: 1463: 1458: 1456: 1451: 1449: 1444: 1443: 1440: 1422: 1418: 1412: 1396: 1390: 1381: 1366: 1362: 1358: 1354: 1347: 1332: 1328: 1322: 1318: 1314: 1313: 1305: 1297: 1291: 1287: 1281: 1275: 1270: 1266: 1256: 1253: 1251: 1248: 1246: 1243: 1241: 1238: 1236: 1235:Consumer unit 1233: 1231: 1228: 1227: 1221: 1217: 1215: 1211: 1210:lighting desk 1206: 1201: 1199: 1188: 1184: 1182: 1178: 1174: 1170: 1166: 1158: 1155: 1151: 1146: 1137: 1134: 1124: 1122: 1118: 1114: 1103: 1097: 1094: 1091: 1088: 1087: 1086: 1083: 1079: 1072: 1069: 1066: 1063: 1062: 1061: 1055: 1052: 1049: 1046: 1045: 1044: 1041: 1038: 1030: 1021: 1019: 1015: 1010: 1008: 1007:0-86341-373-0 1004: 1000: 996: 992: 988: 983: 979: 977: 973: 964: 960: 956: 952: 949: 945: 941: 936: 935: 934: 925: 914: 909: 902: 897: 890: 885: 878: 873: 870: 869: 868: 864: 862: 858: 854: 849: 848:consumer unit 845: 836: 828: 819: 817: 812: 810: 806: 801: 799: 794: 792: 791: 786: 782: 777: 773: 770: 767: 762: 760: 750: 741: 725: 720: 713: 708: 701: 696: 692: 688: 681: 676: 672: 665: 660: 657: 656: 655: 651: 649: 645: 642: 637: 633: 623: 616: 613: 610: 607: 606: 602: 599: 596: 593: 592: 588: 585: 582: 579: 578: 574: 571: 568: 565: 564: 560: 557: 554: 551: 550: 546: 543: 540: 537: 536: 532: 529: 526: 523: 522: 515: 512: 511: 505: 503: 499: 494: 490: 486: 481: 472: 470: 464: 462: 458: 454: 450: 446: 442: 438: 434: 430: 426: 422: 418: 411:North America 408: 406: 405:consumer unit 401: 399: 395: 391: 387: 383: 379: 375: 371: 367: 363: 359: 355: 354:breaker panel 351: 347: 335: 330: 328: 323: 321: 316: 315: 313: 312: 307: 304: 302: 299: 297: 296:Consumer unit 294: 292: 289: 287: 284: 282: 279: 277: 274: 272: 269: 267: 264: 262: 259: 257: 254: 253: 252: 251: 247: 246: 241: 238: 236: 233: 231: 228: 226: 223: 221: 218: 216: 213: 211: 208: 206: 203: 201: 198: 197: 196: 195: 191: 190: 185: 182: 180: 177: 175: 172: 170: 167: 166: 165: 164: 161: 158: 157: 152: 149: 147: 144: 143: 142: 141: 137: 136: 133: 130: 129: 120: 117: 109: 98: 95: 91: 88: 84: 81: 77: 74: 70: 67: â€“  66: 62: 61:Find sources: 55: 51: 45: 44: 39:This article 37: 33: 28: 27: 22: 2123:Net metering 2070:and policies 1988:Power outage 1957:Utility pole 1921:Pumped hydro 1827:distribution 1822:Transmission 1771:Cogeneration 1573:Power factor 1424:. Retrieved 1420: 1411: 1399:. Retrieved 1389: 1380: 1369:. Retrieved 1356: 1346: 1335:. Retrieved 1311: 1304: 1285: 1280: 1269: 1218: 1204: 1196: 1194: 1185: 1162: 1150:service drop 1130: 1109: 1101: 1084: 1080: 1076: 1059: 1042: 1039: 1035: 1011: 984: 980: 969: 931: 922: 865: 847: 841: 813: 805:transformers 802: 795: 788: 784: 778: 774: 771: 763: 755: 738: 670: 652: 629: 622: 513:Split-phase 492: 488: 484: 482: 478: 468: 465: 449:load centers 448: 444: 440: 436: 432: 424: 414: 404: 402: 365: 361: 357: 353: 349: 345: 343: 290: 276:Disconnector 235:Ring circuit 112: 103: 93: 86: 79: 72: 60: 48:Please help 43:verification 40: 2118:Load factor 1973:Black start 1941:Transformer 1642:Natural gas 1593:Variability 1568:Peak demand 1558:Merit order 1488:Backfeeding 469:service box 445:Panelboards 417:sheet metal 2206:Categories 2160:production 2005:Protective 1936:Super grid 1931:Smart grid 1758:Generation 1692:Geothermal 1583:Repowering 1397:. Screwfix 1371:2014-06-15 1337:2014-06-15 1261:References 1255:Switchgear 1165:aesthetics 853:fuse boxes 846:defines a 809:contactors 735:Fuse boxes 648:power cord 425:dead front 396:(RCDs) or 350:panelboard 205:Cable tray 76:newspapers 2068:Economics 1791:Micro CHP 1669:Renewable 1652:Petroleum 1647:Oil shale 1533:Grid code 1493:Base load 1181:basements 1014:CPN Cudis 641:NEMA 5-15 519:Breakers 386:enclosure 106:June 2014 2191:Category 1978:Brownout 1766:AC power 1476:Concepts 1365:Archived 1331:Archived 1224:See also 1133:DIN rail 972:DIN rail 928:Examples 790:isolator 781:DIN rail 691:amperage 626:Interior 516:3-phase 461:grounded 374:circuits 362:fuse box 2007:devices 1717:Thermal 1712:Osmotic 1707:Current 1687:Biomass 1677:Biofuel 1659:Nuclear 1616:Sources 1401:5 March 1363:: 160. 1214:DMX-512 1177:garages 1169:closets 1121:neutral 1073:Heating 1070:Shower, 1001::2001, 999:BS 7671 991:Britain 844:BS 7671 785:incomer 759:busbars 687:toggles 646:with a 457:bonding 441:plug-in 437:bolt-on 429:Busbars 90:scholar 1702:Marine 1682:Biogas 1323:  1292:  1198:dimmer 1173:attics 1154:ampere 1102:etc.. 1060:RCD 2 1056:Cooker 1043:RCD 1 1005:  976:busbar 798:busbar 636:busbar 491:, and 390:switch 366:DB box 92:  85:  78:  71:  63:  2059:(GFI) 1948:(TSO) 1734:Solar 1722:Tidal 1697:Hydro 1426:6 May 1179:, or 1157:fuses 958:RCDs. 944:RCBOs 857:fuses 766:RCBOs 97:JSTOR 83:books 1825:and 1744:Wind 1727:Wave 1637:Coal 1428:2015 1403:2016 1321:ISBN 1290:ISBN 1200:rack 1117:live 1003:ISBN 955:RCDs 948:AFDD 940:MCBs 816:IP2X 378:fuse 281:Fuse 261:ELCB 256:AFCI 69:news 1018:LED 603:12 600:11 589:10 433:hot 380:or 364:or 52:by 2208:: 1419:. 1359:. 1355:. 1329:. 1175:, 1171:, 617:â‹® 614:â‹® 611:â‹® 608:â‹® 597:C 594:B 586:9 583:B 580:A 575:8 572:7 569:A 566:B 561:6 558:5 555:C 552:A 547:4 544:3 541:B 538:B 533:2 530:1 527:A 524:A 504:. 487:, 463:. 407:. 360:, 356:, 352:, 344:A 1461:e 1454:t 1447:v 1430:. 1405:. 1374:. 1340:. 1298:. 1159:. 493:C 489:B 485:A 333:e 326:t 319:v 119:) 113:( 108:) 104:( 94:· 87:· 80:· 73:· 46:. 23:.

Index

Fuse box (disambiguation)

verification
improve this article
adding citations to reliable sources
"Distribution board"
news
newspapers
books
scholar
JSTOR
Learn how and when to remove this message
Electrical installations
North American practice
United Kingdom practice
Regulation of electrical installations
BS 7671 UK wiring regulations
IEC 60364 IEC international standard
Canadian Electrical Code (CE Code)
U.S. National Electrical Code (NEC)
AC power plugs and sockets
Cable tray
Electrical conduit
Mineral-insulated copper-clad cable
Multiway switching
Steel wire armoured cable
Ring main unit
Ring circuit
Thermoplastic-sheathed cable
AFCI

Text is available under the Creative Commons Attribution-ShareAlike License. Additional terms may apply.

↑